X20 system modules • X20 CPUs • X20CP158x and X20CP358x
X20 system User's Manual 3.10
915
Product ID
X20CP1583
X20CP1584
X20CP1585
X20CP1586
Diagnostics
RS232 data transfer
Yes, using status LED
Module run/error
Yes, using status
LED and software
Yes, with status LED
and software status
Yes, using status
LED and software
Yes, with status LED
and software status
Overload
Yes, using status
LED and software
Yes, with status LED
and software status
Yes, using status
LED and software
Yes, with status LED
and software status
Electrical isolation
I/O feed - I/O supply
No
CPU/X2X Link feed - CPU/X2X Link
supply
Yes
Controller
CompactFlash slot
1
Real-time clock
Nonvolatile, 1 s resolution, -10 to 10 ppm accuracy at 25°C
FPU
Yes
Processor
Type
ATOM™ E620T
ATOM™ E640T
Atom™ E680T
Clock frequency
333 MHz
0.6 GHz
1.0 GHz
1.6 GHz
L1 cache
Data code
24 kB
Program code
32 kB
L2 cache
-
512 kB
Integrated I/O processor
Processes I/O data points in the background
Modular interface slots
1
Remanent variables
Max. 64 kB
4)
Max. 256 kB
4)
Max. 1 MB
4)
Shortest task class cycle time
800 µs
400 µs
200 µs
100 µs
Typical instruction cycle time
001 µs
0.0075 µs
00044 µs
0.0027 µs
Data buffering
Battery monitoring
Yes
Lithium battery
Min. 2 years at 23°C ambient temperature
Standard memory
RAM
128 MB DDR2 SDRAM
256 MB DDR2 SDRAM
512 MB DDR2 SDRAM
User RAM
1 MB SRAM
5)
Interfaces
IF1 interface
Signal
RS232
Design
Connection made using 12-pin X20TB12 terminal block
Max. distance
900 m
Transfer rate
Max. 115.2 kbit/s
IF2 interface
Signal
Ethernet
Design
1x shielded RJ45 port
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
10/100/1000 Mbit/s
Transmission
Physical interfaces
10 BASE-T/100 BASE-TX/1000 BASE-T
Half-duplex
Yes
Full-duplex
Yes
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
IF3 interface
Fieldbus
POWERLINK (V1/V2) managing or controlled node
Type
Type 4
6)
Type 4
7)
Type 4
6)
Type 4
7)
Design
1x shielded RJ45 port
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
100 Mbit/s
Transmission
Physical interfaces
100 BASE-TX
Half-duplex
Yes
Full-duplex
No
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
IF4 interface
Type
USB 1.1/2.0
Design
Type A
IF5 interface
Type
USB 1.1/2.0
Design
Type A
IF6 interface
Fieldbus
X2X Link master
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Table 277: X20CP1583, X20CP1584, X20CP1585, X20CP1586 - Technical data