X20 system modules • Digital output modules • X20DO4633
X20 system User's Manual 3.10
1189
4.15.15.14.9.3 Define the OSP digital output value
Name:
CfgOSPValue
This register contains the digital output value, which is output in "Replace with static value" mode during OSP
operation.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Name
Value
Information
0
0 or 1
OSP output value for channel DigitalOutput00
...
...
x
0 or 1
OSP output value for channel DigitalOutput0x
Warning!
The "OSPValue" is not accepted by the module until the "OSPValid" bit has been set in the module.
4.15.15.14.9.4 Define the OSP analog output value
Name:
CfgOSPValue01 to CfgOSPValue04
This register contains the analog output value, which is output in "Replace with static value" mode during OSP
operation.
Data type
Value
USINT
0 to 100
Warning!
The "OSPValue" is not accepted by the module until the "OSPValid" bit has been set in the module.
4.15.15.14.10 Minimum cycle time
The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring.
It should be noted that very fast cycles decrease the idle time available for handling monitoring, diagnostics and
acyclic commands.
Minimum cycle time
All channels
150 μs
4.15.15.14.11 Minimum I/O update time
The minimum I/O update time defines how far the bus cycle can be reduced while still allowing an I/O update to
take place in each cycle.
Minimum I/O update time
All channels
150 μs