4.25.5.5 Connection elements
In accordance with the EN60204-1 standard, a cable cross section of 1.5 mm² or larger must be used for the motor
outputs in order to handle the maximum motor current of 10 A. To ensure full motor power, voltage drops that could
result from the cable length and the electrical connections must also be taken into consideration when selecting
the attachment cable.
Warning!
The terminal block is not permitted to be plugged in or unplugged during operation.
Information:
Shielded motor cables must be used in order to meet the limits according to the EN55011 standard
(emissions).
X1 terminal block
DI 1 - 8 / PWM 1 + 2
X2 terminal block
DI 9 - 16 / PWM 3 + 4
X3 terminal block
Module supply
4.25.5.5.1 Terminal block X1 - DI 1 - 8 / PWM 1 + 2
13 14
15 16
M4
9 10
11 12
M3
X
20
M
M
4
45
6
5 6
7 8
M2
1 2
3 4
M1
r
e
PWM 1+
PWM 1-
DI 5
DI 6
DI 1
DI 3
DI 2
DI 4
DI 7
PWM 2+
DI 8
PWM 2-
4.25.5.5.2 Terminal block X2 - DI 9 - 16 / PWM 3 + 4
13 14
15 16
M4
9 10
11 12
M3
X
20
M
M
4
45
6
5 6
7 8
M2
1 2
3 4
M1
r
e
PWM 3+
PWM 3-
DI 13
DI 14
DI 9
DI 11
DI 10
DI 12
DI 15
PWM 4+
DI 16
PWM 4-