X20 system modules • Other functions • X20DS438A
X20 system User's Manual 3.10
2253
4.26.5.9.3 General module properties
The module has the option of supplying power to IO-Link devices.
To prevent damage to hardware, each channel is monitored individually and equipped with its own overload pro-
tection. In this way, an overload in the power supply on one channel does not affect the other channels.
4.26.5.9.3.1 Configuring overload protection for the IO-Link supply
Name:
CfO_SupplyConfig
This register can be used to define how the module supply behaves for all channels when an overload occurs.
The following rules apply:
•
The overload duration (bits 6-7) corresponds to the time that the supply remains switched on after an
overload is detected. The supply is only cut off if the overcurrent occurs for the entire time configured.
•
The switch-off duration (bits 4-5) corresponds to the time that the supply remains switched off after a
overload-related cutoff until it is switched back on.
For this reason, an overload that occurs over a longer period can cause the module supply to cyclically
switch on/off.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
0 - 3
Reserved
-
00
5 ms
01
20 ms
10
50 ms
4 - 5
Switch-off duration after overload
11
Forbidden
00
1 ms
01
4 ms
10
10 ms
6 - 7
Overload duration until error detection
11
Forbidden
4.26.5.9.3.2 OperatingMode
Name:
CfO_OperatingMode01 to CfO_OperatingMode04
This register is the same as the first bytes of the ChannelMode register in the IO-Link configuration.
It can be used to switch a channel's mode at runtime. The rest of the settings for the ChannelMode register are
unchanged and continue to be used in the selected mode.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
00
Mode: Inactive
01
Mode: SIO output
The channel's C/Q connector is configured as a digital output.
10
Mode: SIO input
The channel's C/Q connector is configured as a digital input.
0 - 1
Channel mode
11
Mode: Operate
The channel's C/Q connector is configured for IO-Link data transfer.
2 - 7
Reserved
-