X20 system modules • Other functions • X20PD0016
X20 system User's Manual 3.10
2319
4.26.8.7 Register description
4.26.8.7.1 Function model 1 - Standard
Read
Write
Register
Fixed offset Name
Data type
Cyclic
Non-cyclic
Cyclic
Non-cyclic
USINT
StatusFuse
Bit 0
0
1
StatusPowerSupply
Bit 1
●
2
2
USINT
●
Fixed modules require their data points to be in a specific order in the X2X frame. Cyclic access occurs according
to a predefined offset, not based on the register address.
Non-cyclic access continues to be based on the register numbers.
4.26.8.7.2 Function model 254 - Bus controller
Read
Write
Register
Offset
1)
Name
Data type
Cyclic
Non-cyclic
Cyclic
Non-cyclic
USINT
StatusFuse
Bit 0
0
0
StatusPowerSupply
Bit 1
●
2
2
USINT
●
1)
The offset specifies the position of the register within the CAN object.
4.26.8.7.3 Module status
Name:
Module status
StatusFuse
StatusPowerSupply
This register can be used to read the status of the power supply.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
0
Fuse OK
StatusFuse
1
Fuse not OK
0
Level of fed voltage OK
0
StatusPowerSupply
1
Level of fed voltage not OK
2 - 7
Reserved
-
4.26.8.7.4 Counter for the voltage dips
Name:
Counter01
This register is used to count how often the voltage dips on the PD module.
Data type
Value
USINT
0 to 255
4.26.8.7.5 Minimum cycle time
The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring.
It should be noted that very fast cycles decrease the idle time available for handling monitoring, diagnostics and
acyclic commands.
Minimum cycle time
100 μs
4.26.8.7.6 Minimum I/O update time
The minimum I/O update time defines how far the bus cycle can be reduced while still allowing an I/O update to
take place in each cycle.
Minimum I/O update time
100 µs
Summary of Contents for X20 System
Page 2: ......