4.3.14.2 Order data
Model number
Short description
Analog input modules
X20AP3111
X20 energy measurement module, 3 analog inputs 480 VAC, 50/60 Hz, 4 analog inputs 20 mA AC,
calculates effective, reactive and apparent power/energy, calculates root mean square values,
240 V keyed
X20AP3121
X20 energy measurement module, 3 analog inputs 480 VAC, 50/60 Hz, 4 analog inputs 1 A AC,
calculates effective, reactive and apparent power/energy, calculates root mean square values,
240 V keyed
X20AP3131
X20 energy measurement module, 3 analog inputs 480 VAC, 50/60 Hz, 4 analog inputs 5 A AC,
calculates effective, reactive and apparent power/energy, calculates root mean square values,
240 V keyed
X20AP3161
X20 energy measurement module, 3 analog inputs 480 VAC, 50/60 Hz, 4 analog inputs 333
mV AC, calculates effective, reactive and apparent power/energy, calculates root mean square
values, 240 V keyed
Required accessories
Bus modules
X20BM32
X20 bus module for double-width modules, 240 VAC keyed, internal I/O supply continuous
Terminal blocks
X20TB32
X20 terminal block, 12-pin, 240 VAC keyed
Table 68: X20AP3111, X20AP3121, X20AP3131, X20AP3161 - Order data
4.3.14.3 Technical data
Product ID
X20AP3111
X20AP3121
X20AP3131
X20AP3161
Short description
I/O module
3-phase power and energy measurement module
General information
B&R ID code
0xC9DA
0xC9DB
0xC9DC
0xE17B
Status indicators
I/O function per channel, operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Inputs
Yes, using status LED and software
Power consumption
Bus
0.85 W
Internal I/O
-
Additional module power dissipation
[W]
40 mW
1)
2 W
1)
-
2)
Electrical isolation
Channel - Bus
Yes
Channel - Channel
No
Isolation voltage
Inputs - Bus / I/O supply
5500 VDC
Inputs - Ground
5500 VDC
Bus / I/O supply - Ground
510 VAC
Certification
CE
Yes
cULus
Yes
-
ATEX Zone 2
Yes
-
GOST-R
Yes
Voltage inputs
Number of phases
3
Nominal voltage
Between phases
Max. 480 VAC
Phase to N
Max. 277 VAC
Max. overload voltage
1.5 x U
N
permanent
2 x U
N
for 1 min
Table 69: X20AP3111, X20AP3121, X20AP3131, X20AP3161 - Technical data