4.4.3.10.6.1 HART - Configuration
HART modules are analog modules equipped with a HART modem. For each channel, a separate HART network
can be managed by the module, which acts as a primary master. Once configured successfully, the HART infor-
mation is stored in the module where it can then be used by the PLC.
The number of HART slaves must be specified in the configuration.
If only one slave is connected to the HART channel, then it is part of a point-to-point network. The module can then
prepare up to four process variables from the connected slave.
Multidrop mode allows up to 15 HART slaves to be connected. The primary process variable from each slave is
then retrieved.
HartNodeCnt
Name:
HartCodeCnt_1 to HartCodeCnt_2
These registers tell the module how many HART slaves are connected to a channel.
Information:
If a slave is not connected to one of the HART channels, the value "0" should be defined in this register.
This shortens the I/O update time and avoids superfluous error messages.
Data type
Value
Information
0
HART communication disabled for this channel
1
Point-to-point
Standard HART communication (bus controller default)
USINT
2 to 15
Multidrop
Number of HART slave nodes
HartBurstNode
Name:
HartBurstNode_1 to HartBurstNode_2
In addition to the type of network, the user can also choose from two different types of communication behavior.
Conventional HART communication relies on polling. The module requests the data from the individual HART
slaves and receives the corresponding information from each slave as a response. If a HART node should be
queried in short time intervals, the user can configure burst mode for channels on one node. In this case, the slave
transmits the node's information cyclically without constant prompting from the master.
The "HartBurstNode" registers are therefore used to enter the node numbers (short address) for the chan-
nels whose information should be retrieved using burst mode. Burst mode itself is enabled with the
"HartMode""HartMode" register.
Data type
Value
Information
USINT
0 to 15
Point-to-point
0 (bus controller default)