Technical data • Individual components
92
Panel PC 2100 swing arm user's manual V1.12
3.4.2 5ACCIF01.FPCS-000
3.4.2.1 General information
Interface option 5ACCIF01.FPSC-000 is equipped with a POWERLINK, RS485 and CAN bus master interface. 32
kB of FRAM is also installed.
•
1x POWERLINK interface managing or controlled node
•
1x CAN bus master interface
•
1x RS485 interface
•
32 kB FRAM
•
Compatible with the APC2100 and PPC2100
This interface option can only be operated with Automation Runtime.
3.4.2.2 Order data
Model number
Short description
Figure
Interface options
5ACCIF01.FPCS-000
Interface card - 1x RS485 interface - 1x CAN interface - 1x POW-
ERLINK interface - 32 kB FRAM - For APC2100/PPC2100 - On-
ly available with a new device
Optional accessories
Terminal blocks
0TB1210.3100
Connector 300 VDC - 10-pin female - Cage clamp terminal block
- Protected against vibration by the screw flange
Table 80: 5ACCIF01.FPCS-000 - Order data
3.4.2.3 Technical data
Model number
5ACCIF01.FPCS-000
General information
LED status indicators
L1, L2, L3
B&R ID code
0xED7C
Certification
CE
Yes
UL (cULus)
LISTED UL 508 E115267
UL HazLoc (cULus)
Cl. I, Div. 2 ABCD BR T4
1)
Controller
FRAM
Size
32 kB
Remanent variables in power failure mode
32 kB
(e.g. for Automation Runtime, see Automation Help)
Interfaces
COM
Quantity
1
Type
RS485, not electrically isolated
Design
10-pin, male
UART
16550-compatible, 16-byte FIFO
Max. baud rate
115 kbit/s
POWERLINK
Quantity
1
Transfer
100 Base-TX
Type
Type 4
2)
Design
Shielded RJ45
Transfer rate
100 Mbit/s
Cable length
Max. 100 m between two stations (segment length)
CAN
Quantity
1
Design
10-pin, male, not electrically isolated
Transfer rate
Max. 1 Mbit/s
Terminating resistor
Type
Can be enabled or disabled using a slide switch
Electrical characteristics
Power consumption
1.75 W
Operating conditions
EN 61131 pollution degree
Pollution degree 2
Table 81: 5ACCIF01.FPCS-000 - Technical data