Technical data • Individual components
Chapter 2
Technical data
Panel PC 2100 swing arm user's manual V1.12
93
Model number
5ACCIF01.FPCS-000
Environmental conditions
Temperature
Operation
-20 to 55°C
Storage
-20 to 60°C
Transport
-20 to 60°C
Relative humidity
Operation
5 to 90%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Weight
25 g
Table 81: 5ACCIF01.FPCS-000 - Technical data
1)
Yes, although applies only if all components installed within the complete system have this certification and the complete system itself carries the corre-
sponding
mark.
2)
More information is available in Automation Help (Communication - POWERLINK - General information - Hardware - IF / LS).
3.4.2.3.1 POWERLINK interface - Pinout
The POWERLINK interface on the system unit is referred to as IF1.
POWERLINK - IF1
1)2)
Cabling
S/STP (Cat 5e)
Cable length
Max. 100 m (min. Cat5e)
Status LED
On
Off
Green
See Status/Error LED.
Link LED
On
Off
Yellow
Link (POWERLINK net-
work connection available)
Activity (blinking - da-
ta transfer in progress)
RJ45, female
1
Status LED
Link LED
Table 82: 5ACCIF01.FPCS-001 - POWERLINK interface
1)
The interfaces, etc. available on the device or module have been numbered as such for easy identification. This numbering may differ from that used by
the particular operating system.
2)
This interface is referred to as IF1 in Automation Studio / Automation Runtime.
3.4.2.3.2 COM serial interface - Pinout
The COM serial interface on the system unit is referred to as IFx.
Serial interface COM - IFx
1)2)
RS485
Type
RS485, not electrically isolated
UART
16550-compatible, 16-byte FIFO
Transfer rate
Max. 115 kbit/s
Bus length
Max. 1200 m
Pin
Assignment
1
-
2
Shield
3
-
4
-
5
-
6
-
7
-
8
COM GND
9
DATA\
10
DATA
10-pin, male
1 3 5 7
2 4 6 8 10
9
Table 83: 5ACCIF01.FPCS-000 - COM interface
1)
The interfaces, etc. available on the device or module have been numbered as such for easy identification. This numbering may differ from that used by
the particular operating system.
2)
This interface can only be used in Automation Runtime and is referred to as IF7 in Automation Studio / Automation Runtime. It is not a "PC interface" and
therefore not shown in BIOS.
The RTS line must be switched by the driver for each transmission or reception; there is no automatic switch-
back mechanism.