International and national certifications
Power Panel C50 User's manual V1.10
71
Toppling / Transport (packaged)
Testing performed per stan-
dard:
EN 60068-2-31
Requirements per standard:
EN 60721-3-2 / Class 2M1
Requirements per standard:
EN 60721-3-2 / Class 2M2
Requirements per standard:
EN 60721-3-2 / Class 2M3
Weight
Required
Weight
Required
Weight
Required
<20 kg
Yes
<20 kg
Yes
<20 kg
Yes
20 to 100 kg
-
20 to 100 kg
Yes
20 to 100 kg
Yes
>100 kg
-
>100 kg
-
>100 kg
Yes
Toppling
Transport (packaged)
Topple on all edges
Topple on all edges
Topple on all edges
9.2.5 Electrical safety
Overvoltage category
Requirement per standard: EN 61131-2
Explanation per standard: EN 60664-1
Overvoltage category II
Equipment of "Overvoltage category II" is energy-consuming equipment to be supplied by the fixed in-
stallation.
Pollution degree
Requirement per standard: EN 61131-2
Explanation per standard: EN 60664-1
Pollution degree 2
Only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by con-
densation is to be expected.
Protection rating provided by enclosure (IP code)
Requirement per standard:
EN 61131-2
Explanation of code num-
bers
per standard: EN 60529
Meaning for the
protection of equipment
Meaning for the
protection of personnel
First number
IP
2
x
Protected against solid foreign bodies with a
diameter ≥12.5 mm
Protected against touching dangerous parts
with fingers
Back: ≥IP20
Second number
IPx
0
Not protected.
-
Requirement per
manufacturer
Explanation of code num-
bers
per standard: EN 60529
Meaning for the
protection of equipment
Meaning for the
protection of personnel
First number
IP
5
x
Protected against dust.
Protected against touching dangerous parts
with conductor.
Front: IP55
Second number
IP x
5
Protected against water jets.
-