Technical data
16
Automation Panel 9xD - Hygienic design User's manual V 1.80
4 Technical data
4.1 Complete system
4.1.1 Connection options
The Automation Panel can be connected to a B&R industrial PC via SDL, DVI SDL3 or SDL4 operations. The
connection options described below provide an overview of the operating modes and possible limitations.
4.1.1.1 SDL operation
4.1.1.1.1 SDL operation without USB cable (mode 1)
With this connection option, all communication between the Automation Panel and B&R industrial PC takes place
via a single SDL cable.
In addition to the display data, information from the touch screen, matrix keys, LEDs and service/diagnostic data is
transferred. The Automation Panel can be installed up to 40 m away from the B&R industrial PC. USB 1.1 is also
transferred over this distance and fully integrated into SDL. External adapter modules are not required.
The brightness of the display can be set via the B&R Control Center, for example.
Automation Panel
with SDL/DVI receiver
B&R industrial PC
SDL cable
Power supply (SELV/PELV)
Availability of the interfaces on the Automation Panel with SDL/DVI receiver:
Panel In
✓
USB In
x
Power supply
✓
Brightness controls
x
USB1, USB2
✓
USB 1.1
COM interface for touch
screen
x
Grounding
✓
Maximum cable length: 40 m
Requirements
•
Automation Panel with SDL/DVI receiver
•
B&R industrial PC with SDL interface
•
SDL cable