Standards and certifications • Requirements for immunity to disturbances (immunity)
Automation PC 620 with 945GME N270 CPU board User's Manual V 1.10
4. Requirements for immunity to disturbances (immunity)
Evaluation criteria according to EN 61000-6-2
Criteria A:
The operating equipment must continue to work as intended
during
the test. There should be
no interference in the operating behavior and no system failures below a minimum operating
quality as defined by the manufacturer.
Criteria B:
The operating equipment must continue to work as directed
after
the test. There should be no
interference in the operating behavior and no system failures below a minimum operating quality
as defined by the manufacturer.
Criteria C:
A temporary function failure is permitted if the function restores itself, or the function can be
restored by activating configuration and control elements.
Criteria D:
Impairment or failure of the function, which can no longer be established (operating equipment
destroyed).
Immunity
Test carried out according to
Limits according to
Electrostatic discharge (ESD)
EN 61000-4-2
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Immunity against high-frequency
electromagnetic
fields (HF field)
EN 61000-4-3
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Immunity to high-speed transient
electrical disturbances (burst)
EN 61000-4-4
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Immunity to surge voltages
EN 61000-4-5
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Immunity to conducted
disturbances
EN 61000-4-6
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Immunity against magnetic fields
with electrical frequencies
EN 61000-4-8
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Immunity to voltage dips, short-
term interruptions and voltage
fluctuations
EN 61000-4-11
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Immunity to damped vibration
EN 61000-4-12
EN 61000-6-2: Generic standard (industrial areas)
EN 61131-2: Programmable logic controllers
Table 242: Overview of limits and testing guidelines for immunity
Summary of Contents for Automation PC 620
Page 2: ...2 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Page 4: ...4 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Page 6: ...6 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Page 568: ...568 Appendix A Glossary Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...