Technical data
Mobile Panel 7200 User's manual V 1.01
33
2.3.2.2.2 5CAMPC.0020-11
2.3.2.2.2.1 General information
A straight-through control cabinet cable is required for the wiring inside the control cabinet.
The pinout of the Ethernet connector makes it possible to connect directly to a standard Ethernet hub.
Information:
The control cabinet cable is used for all Mobile Panel product series. Not all wires are used when wiring
the MP7x00 and MP40/50. Functionality therefore differs from MP100/200 devices.
The surface is protected against water, oil (lubricating and hydraulic oils per EN 60811 Part 2-1) and cooling
lubricant.
The control cabinet cable is secured to the control cabinet door via the connection housing (see
). The other end of the control cabinet cable has a pre-assembled RJ45 Ethernet
connector. The other connecting cables are open with wire end sleeves to simplify further wiring to the safety
equipment and other connections.
2.3.2.2.2.2 Order data
Model number
Short description
Figure
Control cabinet cables
5CAMPC.0020-11
Mobile Panel control cabinet cable - Push-Pull circular connector
- Ethernet straight-through - 2 m
Optional accessories
Accessories
4MPCBX.0000-00
Mobile Panel connection box - For cables with push-pull circular
connectors
4MPCBX.0001-00
Mobile Panel small connection box - For cables with push-pull
circular connectors
Table 7: 5CAMPC.0020-11 - Order data
2.3.2.2.2.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for these individual
components and may differ from those of the complete system. The data specified for the complete
system applies to the complete system in which this individual component is used, for example.
Model number
5CAMPC.0020-11
General information
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
Cable construction
Type
Straight-through
Supply lines
Conductor resistance
≤30 Ω/km
Material
Tinned copper stranded wire
Permissible operating voltage
30 VDC
Outer jacket
Material
Silicone- and halogen-free, flame-retardant PUR outer jacket
Color
Similar to RAL 7012
Cable elements
Control devices
Direct connection between control devices and monitoring device (6 wires)
(2 wires not used on the MP40/50 and MP7x00)
CAN
2 pairs with shielding (5 wires)
Not used on the MP40/50 and MP7x00
Network
Twisted pair cable for Ethernet (10/100 Mbit/s)
(4 wires, RJ45 connector)
Serial
3 wires
Not used on MP40/50 and MP7x00
Power supply
+24 VDC supply voltage and grounding (3 wires), SELV
1)
Enable switch
Direct connection between enable switch and monitoring device (6 wires)
(2 wires not used on the MP40/50 and MP7x00)
Connector
Type
Receptacle for push-pull locking mechanism
Table 8: 5CAMPC.0020-11 - Technical data