Technical data • Individual components
112
Power Panel 500 user's manual V1.40
Product ID
5PP5IF.FPLM-00
Environmental conditions
Temperature
Operation
0 to 55°C
Storage
-20 to 60°C
Transport
-20 to 60°C
Relative humidity
Operation
5 to 90%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Table 62: 5PP5IF.FPLM-00 - Technical data
1)
Yes, although applies only if all components installed within the complete system have this certification.
2)
With optimized access using write combining
3.4.4.3.1 POWERLINK interface
POWERLINK
Cabling
S/STP (Cat 5e)
Cable length
Max. 100 m (min. Cat 5e)
Speed LED
On
Off
Green/Red
see Status / Error LED
Link LED
On
Off
Yellow
Link (POWERLINK net-
work connection available)
Activity (blinking - da-
ta transfer in progress)
Female RJ45 connector
1
Speed LED
Link LED
Table 63: 5PP5IF.FPLM-00 - POWERLINK interface
3.4.4.3.2 Status/Error LED
The Status/Error LED is a green and red dual LED. The LED status can have different meanings depending on
the operating mode.
Ethernet mode
In this mode, the interface is operated as an Ethernet interface.
Green - Status
Description
On
Interface being operated as an Ethernet interface
Table 64: Status/Error LED - Ethernet mode
POWERLINK V1
LED status indicators
Green
Red
Status of the POWERLINK station
On
Off
The POWERLINK station is running with no errors.
Off
On
A fatal system error has occurred. The error type can be read using the PLC logbook. An irreparable problem has
occurred. The system cannot properly carry out its tasks. This state can only be changed by resetting the module.
Blinking alternately
The POWERLINK managing node has failed. This error code can only occur when operated as a controlled node.
Off
Blinking
System failure. The red blinking LED signals a certain type of error using a blink code (see section "System stop
Table 65: Status/Error LED - POWERLINK V1 operating mode