Technical data • Individual components
84
Power Panel 500 user's manual V1.40
Product ID
5PP520.1214-00
Inserts
Interface board
Yes
I/O board
No
Electrical characteristics
Nominal voltage
24 VDC ±25%
Nominal current
1.2 A
6)
Starting current
Typ. 3 A, max. 50 A for <300 µs
Power consumption
29 W
7)
Electrical isolation
Yes
Operating conditions
EN 60529 protection
Back: IP20 (only with an inserted CF card, IF board or optional IF cover)
Front: IP65, protection from dust and sprayed water
Environmental conditions
Temperature
Operation
0 to 55°C
Storage
-20 to 60°C
Transport
-20 to 60°C
Relative humidity
Operation
See temperature/humidity diagram
Storage
See temperature/humidity diagram
Transport
See temperature/humidity diagram
Vibration
Operation (continuous)
2 to 9 Hz: 1.75 mm amplitude / 9 to 200 Hz: 0.5 g
Operation (occasional)
2 to 9 Hz: 3.5 mm amplitude / 9 to 200 Hz: 1 g
Storage
2 to 8 Hz: 7.5 mm amplitude / 8 to 200 Hz: 2 g / 200 to 500 Hz: 4 g
Transport
2 to 8 Hz: 7.5 mm amplitude / 8 to 200 Hz: 2 g / 200 to 500 Hz: 4 g
Shock
Operation
15 g, 11 ms
Storage
30 g, 6 ms
Transport
30 g, 6 ms
Elevation
Operation
Max. 3000 m (component-dependent)
8)
Mechanical characteristics
Housing
Material
Galvanized steel plate
Front
9)
Frame
Naturally anodized aluminum
Panel overlay
Material
Polyester
Light background
RAL 9006
Dark gray border around display
RAL 7024
Gasket
Flat gasket around display front
Dimensions
Width
362 mm
Height
284 mm
Depth
60.2 mm
Weight
3350 g
Table 41: 5PP520.1214-00 - Technical data
1)
At 50°C, 8.5 µA of the supplied components and a self-discharge of 40%. If an interface board with SRAM has been installed, the service life is 2½ years.
2)
Maintenance Controller Extended.
3)
The COM1 interface is identified in BIOS as the COM A interface.
4)
At an ambient temperature of 25°C. Reducing the brightness by 50% can result in an approximately 50% increase in the half-brightness time.
5)
Touch screen drivers for approved operating systems are available in the Downloads section of the B&R website.
6)
The specified value applies to a nominal voltage of 24 VDC.
7)
The specified value applies to a system unit with a CPU board but without an interface board.
8)
The maximum ambient temperature is typically derated by 1°C per 1000 meters (starting at 500 meters above sea level).
9)
There may be visible deviations in the color and surface appearance depending on the process or batch.