International and national certifications
Power Panel C50 User's manual V1.10
69
Voltage fluctuations
Testing performed per standard:
EN 61000-4-11 / EN 61000-4-29
Requirements per standard:
EN 61131-2 / Zone B
Requirements per standard:
EN 61000-6-2
AC power inputs
-15% / +10%
Test duration per 30 minutes
Criteria A
-
DC power inputs
-15% / +20%
Test duration per 30 minutes
Criteria A
-
9.2.3 Emission requirements
Limit values per standard:
Phenomenon
Testing performed
per standard:
EN 61131-2
1)
EN 61000-6-4
2)
EN 55011 / EN 55022
EN 55016-2-1
✔
✔
EN 55011 / EN 55022
EN 55016-2-3
✔
✔
1)
EN 61131-2: Product standard - Programmable logic controllers
2)
EN 61000-6-4: Generic standards - Emission standard for industrial environments
Emissions related to lines
Testing performed per standard:
EN 55011 / EN 55022 / EN 55016-2-1
Limit values per standard:
EN 61131-2 / Zone B
Limit values per standard:
EN 61000-6-4
150 to 500 kHz
79 dB (µV) quasi-peak value
66 dB (µV) average value
AC mains connection
150 kHz to 30 MHz
500 kHz to 30 MHz
73 dB (µV) quasi-peak value
60 dB (µV) average value
-
150 to 500 kHz
97 to 87 dB (µV) quasi-peak value
53 to 40 dB (µA) quasi-peak value
84 to 74 dB (µV) average value
40 to 30 dB (µA) average value
Telecommunications / network connection
150 kHz to 30 MHz
-
500 kHz to 30 MHz
87 dB (µV) quasi-peak value
43 dB (µA) quasi-peak value
74 dB (µV) average value
30 dB (µA) average value
Radiated emissions
Testing performed per standard:
EN 55011 / EN 55022 / EN 55016-2-3
Limit values per standard:
EN 61131-2 / Zone B
Limit values per standard:
EN 61000-6-4
30 to 230 MHz
40 dB (µV/m) quasi-peak value
Electric field / Measured from 10 m
30 MHz to 1 GHz
230 MHz to 1 GHz
47 dB (µV/m) quasi-peak value
-
1 to 3 GHz
76 dB (µV/m) peak value
56 dB (µV/m) average value
Electric field / Measured from 3 m
1 to 6 GHz
1)
-
3 to 6 GHz
80 dB (µV/m) peak value
60 dB (µV/m) average value
1)
Depending on highest internal frequency