International and national certifications
104
Power Panel C70 User's manual V1.30
Surge voltages (Surge)
Testing performed per standard:
EN 61000-4-5
Requirements per standard:
EN 61131-2 / Zone B
Requirements per standard:
EN 61000-6-2
AC mains inputs/outputs
Line / line
±1 kV
Criteria B
AC mains inputs/outputs
Line / ground
±2 kV
Criteria B
DC mains inputs/outputs
Line / line
±0.5 kV
1)
Criteria B
±0.5 kV
Criteria B
DC power inputs
Line / ground
±0.5 kV
1)
Criteria B
±0.5 kV
Criteria B
DC power outputs
Line / ground
±0.5 kV
1)
Criteria B
±0.5 kV
Criteria B
Signal connections, unshielded
Line / ground
±1 kV
1)
Criteria B
All shielded lines
Line / ground
±1 kV
1)
Criteria B
-
1)
Only for connections with a permitted line length greater than 30 m.
Conducted disturbances
Testing performed per standard:
EN 61000-4-6
Requirements per standard:
EN 61131-2 / Zone B
Requirements per standard:
EN 61000-6-2
AC mains inputs/outputs
10 V
150 kHz to 80 MHz
80% AM (1 kHz)
Criteria A
DC mains inputs/outputs
10 V
150 kHz to 80 MHz
80% AM (1 kHz)
Criteria A
Other I/Os and interfaces
10 V
1)
150 kHz to 80 MHz
80% AM (1 kHz)
Criteria A
1)
Only for connections with a permitted line length greater than 3 m.
Magnetic fields with electrical frequencies
Testing performed per standard:
EN 61000-4-8
Requirements per standard:
EN 61131-2 / Zone B
Requirements per standard:
EN 61000-6-2
Housing, completely wired
30 A/m
3 axes (x, y, z)
50/60 Hz
1)
Criteria A
1)
Mains frequency per manufacturer data
Voltage dips
Testing performed per standard:
EN 61000-4-11
Requirements per standard:
EN 61131-2 / Zone B
Requirements per standard:
EN 61000-6-2
0% residual voltage
250/300 periods (50/60 Hz)
1)
20 attempts
Criteria C
40% residual voltage
10/12 periods (50/60 Hz)
1)
20 attempts
Criteria C
AC power inputs
70% residual voltage
25/30 periods (50/60 Hz)
1)
20 attempts
Criteria C
1)
Mains frequency per manufacturer data
Short-term interruptions
Testing performed per standard:
EN 61000-4-11 / EN 61000-4-29
Requirements per standard:
EN 61131-2 / Zone B
Requirements per standard:
EN 61000-6-2
AC power inputs
0% residual voltage
0.5 periods (50/60 Hz)
1)
20 attempts
Criteria A
0% residual voltage
1 period (50/60 Hz)
1)
3 attempts
Criteria B
DC power inputs
0% residual voltage
≥10 ms (PS2)
2)
20 attempts
Criteria A
-
1)
Mains frequency per manufacturer data
2)
Use of a B&R power supply guarantees that these requirements are met.