Commissioning
88
Power Panel C70 User's manual V1.30
Securing the conductor lines to the grounding plate
1
Ground conductor
The connection to ground potential must be as short as possible and sufficiently strong (≥4 mm²) over the
intended spade terminal (Faston 6.3 mm).
2
Shielded lines
A central ground connection is available to effectively deflect interference. All cable shields must be con-
nected to ground with good conductivity using a cable tie on the grounding plate or some other method.
3
Unshielded lines
All unshielded lines must be relieved of tension by using a cable tie to tie them to the grounding plate.
2
1
3
Grounding in the control cabinet
Control cabinet
Grounding rail
Ground connection
≥4 mm²
Figure: Grounding in the control cabinet
Important!
The ground connection of the device must be low impedance and connected to ground (e.g. grounding
rail in the control cabinet) using a short path.