X90 mobile modules
336
X90 mobile system User's manual V 1.20 - Translation of the original manual
5.7.1.7.9 Module information
5.7.1.7.9.1 Measuring the operating voltage
Name:
SupplyVoltage01
The module voltage can be read out in this register.
Data type
Values
Information
UINT
0 to 32767
Voltage in [mV] from 0 V to 32.767 V
5.7.1.7.9.2 Measuring operating temperature
Name:
Temperature
The module temperature can be read out in this register.
Data type
Values
Information
INT
-550 to 1250