Banner AG4 Series Safety Laser Scanner
Settings
•
0 - 528
•
Default value: 514
6.2
Safety-relevant parameters
6.2.1
Application
The Application parameter provides the usage scenario that the Scanner will be configured for.
Settings
The following applications can be selected.
Depending on the set application, the parameters “Resolution” and “Start/restart interlock” are preset:
Table 7. Application Settings
Selectable application
Resolution
Start/restart interlock
Danger Zone Guarding
70 mm
Activated
Leg detection
50 mm
Activated
Passage control
150 mm
Activated
Arm protection
40 mm
Activated
Hand protection
30 mm
Activated
Body protection
150 mm
Activated
Freely selectable Presetting Activated
Activated
Default value: Danger Zone Guarding
6.2.2
Response times
The Response time parameter is the time that the AG4 needs for its outputs to switch off once an object is detected.
Two response times should be provided:
PF response time: Time until the Scanner switches off the OSSD 1 and OSSD 2 safety outputs or switching function.
WF response time: Time until the Scanner switches off the alarm output.
Settings
Multiple of 40 ms, in the 80 ms - 640 ms range
Default values:
PF response time:
80 ms
WF response time:
80 ms
6.2.3
Dust suppression
The Dust suppression parameter indicates whether or not the
Dust suppression
function is activated.
54
P/N 144924 05/2009
Product Manual