Banner AG4 Series Safety Laser Scanner
Important:
Verify that the Scanner OSSDs switch off whenever
each
of the protective field is entered.
Check to be sure there are no unprotected access routes to the hazard.
See
Commissioning and Check out procedures
in Section 7
15.
Check to make sure that
all
field pairs switch to the
active state
as expected.
16.
Connect the AG4 OSSDs to the machine interface and, under controlled conditions where no personnel are exposed to the hazard, test
the Scanner along and within the boundaries to ensure that the dangerous motion will stop and not start up while an object is in the
protective field.
WARNING . . . FIELD PAIR SWITCHING LIMITATIONS
Field Pair switchover is only permitted during portions of the application cycle where hazards are not present or are otherwise
inaccessible via other guarding means.
Failure to properly control or apply Field Pair switchover operations can result in serious bodily injury or death.
Product Manual
P/N 144924 05/2009
43