Banner AG4 Series Safety Laser Scanner
1 X1 Machine Interface (15-pin sub-D)
2 X2 PC Interface (9-pin sub-D)
3 X2 PC Interface cable
4 X2 Dust/protective cap
Figure 3-16. Scanner Interconnections
3.5.2 Initial Electrical Connections
Ensure that electrical power is not applied to the Scanner until told to do so. Do not connect any wires to the machine
control circuits (i.e., OSSD outputs) at this time.
For the initial power-up and checkout, only the power connections (X1-3 and X1-1), the start/restart (X1-2 if used), and
the Field Pair inputs (X1-4, X1-6, X1-7, and X1-8) should be connected as described below and in Figures 3-18, 3-19,
and 3-20. Final connection of the OSSD and Alarm (Auxiliary) outputs will occur after configuration and the initial
checkout. The user must refer to the installation instructions of any interfacing device (e.g. UM-FM-9A/-11A) for proper
hookup and checkout.
If used, connect the external reset switch to the reset wire (violet) on the Machine Interface cordset and to 24V dc (see
Figures 3-18 and 3-20). See warning in Section 3.3.3 about the physical location of the reset switch. The reset switch
must be a normally open switch that is held closed for approximately 1/4 second, but no longer than 5 seconds, and then
re-opened to accomplish the reset. The switch must be capable of switching 10 to 30V dc at 30 mA.
3.6 Scanner Initial Checkout
The initial checkout procedure must be performed by a Qualified Person (see Section 4.1). It must be performed only
after configuring the System and after connections are made per Section 3.5.
Initial checkout is performed on two occasions:
1. To ensure proper installation when the System is first installed, and
2. To ensure proper System function whenever any maintenance or modification is performed on the System or
on the machinery being guarded by the System. (See Section 6.1 for a schedule of required checkouts.)
For the initial checkout, the Scanner must be checked without power being available to the guarded machine.
Final interface connections to the guarded machine cannot take place until the Scanner has been checked out.
This may require lockout/tagout procedures (refer to OSHA1910.147, ANSI Z244-1, or the appropriate standard for
controlling hazardous energy). These connections will be made after the initial checkout procedure has been
successfully completed.