Units Description
Definition
8
Temp °C (Low
Res)
Celsuis, low resolution. To measure a greater temperature range, use the low resolution unit. In low resolu-
tion mode, temperature = (Modbus register value) ÷ 2.
LCD: 0000.0C
9
Temp °F (Low
Res)
Fahrenheit, low resolution. To measure a greater temperature range, use the low resolution unit. In low
resolution mode, temperature = (Modbus register value) ÷ 2.
LCD: 0000.0F
10
Asynchronous
Counter, 32-bit
The 32-bit counter value records counts up to 4.29 billion.
LCD: 0000 0000
11
Asynchronous
Counter, 16-bit
The 16-bit counter value records counts up to 65535.
LCD: 0000
Output Units
Units Description
Definition
0
Raw
Displays the raw A/D conversion data with data ranges from 0 to 65535. This units type is typically used
only for factory calibration.
LCD: Raw A/D hex value
1
4 to 20 mA
Analog unit. Modbus register contents are scaled such that 0 represents 4 mA and 65535 represents 20
mA.
LCD: 4.00mA–20.00mA
2
0 to 20 mA
Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and 65535
represents 20 mA.
LCD: 0.00mA–20.00mA
3
Discrete (ON/
OFF)
Default discrete unit.
LCD: ON/OFF
4
0 to 10V (Volts) Analog unit using 0 to 10V instead of current. Modbus register contents are scaled such that 0 represents
0V and 65535 represents 10V.
LCD: 0.00V–10.00V
5
Signed Analog,
0 to 10V
For a signed value, such as temperature, that is to be converted to a voltage out value. Use null to set the
start point and span to define the range. The null value is the starting temperature to be associated with
0V. The span is the entire temperature range that is to be associated with 0 to 10V.
LCD: 0.00V–10.00V
6
Signed Analog,
0 to 20 mA
For a signed value, such as temperature, that is to be converted to a mA out value. Use null to set the start
point and span to define the range. The null value is the starting temperature to be associated with 0 mA.
The span is the entire temperature range that is to be associated with 0 to 20 mA.
LCD: 0.00mA–20.00mA
7
Unsigned Ana-
log, 0 to 20 mA
For unsigned values, such as a counter, that is to be converted to a mA out value. Use the null to set the
start point and span to define the range. The null value is the distance to be associated with 0 mA. The
span is the entire distance range that is to be associated with 0 to 20 mA.
LCD: 0.00mA–20.00mA
SureCross Wireless I/O Network Manual
rev. I
www.bannerengineering.com - tel: 763-544-3164