Battery Replacement
DX81 and DX81H FlexPower Module Battery Replacement
For outside or high humidity environments, conductive grease may be applied to the battery terminals to prevent moisture and corrosion
buildup.
To replace the lithium "D" cell battery in the DX81 FlexPower
™
battery kit, follow these steps.
1. Unplug the battery device from the SureCross device it powers.
2. Remove the four screws mounting the battery pack face plate to the body and remove
the face plate.
3. Remove the discharged battery and replace with a new battery. Only use a 3.6V lithium
battery from Xeno, model number XL-205F.
4. Verify the battery’s positive and negative terminals align to the positive and negative ter-
minals of the battery holder mounted within the case. Caution: There is a risk of explo-
sion if the battery is replaced incorrectly.
5. After replacing the battery, allow up to 60 seconds for the device to power up.
When removing the battery, press the battery towards the negative terminal to compress the
spring. Pry up on the battery’s positive end to remove from the battery holder. Properly dispose
of your used battery according to local regulations by taking it to a hazardous waste collection
site, an e-waste disposal center, or any other facility qualified to accept lithium batteries.
As with all batteries, these are a fire, explosion, and severe burn hazard. Do not burn or expose
them to high temperatures. Do not recharge, crush, disassemble, or expose the contents to
water.
Replacement battery model number: BWA-BATT-001. For pricing and availability, contact Banner Engineering.
DX81P6 FlexPower
™
Module Battery Replacement
To replace the lithium "D" cell battery pack in the DX81P6 FlexPower
™
battery kit, follow these steps.
1. Unplug the battery device from the SureCross device it powers.
2. Remove the four screws mounting the clear plastic battery pack cover to the
housing.
3. Remove the cover and foam spacer.
4. Disconnect the discharged battery pack.
5. Remove the discharged battery pack and replace with a new battery pack. Cau-
tion: There is an explosion risk if the battery pack is replaced incorrectly.
6. After replacing the battery pack, allow up to 60 seconds for the device to power
up.
Properly dispose of the used battery packs according to local regulations by taking it
to a hazardous waste collection site, an e-waste disposal center, or any other facility
qualified to accept lithium batteries.
As with all batteries, these are a fire, explosion, and severe burn hazard. Do not burn
or expose them to high temperatures. Do not recharge, crush, disassemble, or expose
the contents to water.
SureCross Wireless I/O Network Manual
84
www.bannerengineering.com - tel: 763-544-3164
rev. I