Specifications
Radio Range1
900 MHz, 150 mW: Up to 4.8 km (3 miles)
2.4 GHz, 65 mW: Up to 3.2 km (2 miles)
Minimum Separation Distance
900 MHz (150 mW): 2 m (6 ft)
2.4 GHz (65 mW): 0.3 m (1 ft)
Transmit Power
900 MHz, 150 mW: 21 dBm (150 mW) conducted
2.4 GHz, 65 mW: 18 dBm (65 mW) conducted, less than or equal to 20
dBm (100 mW) EIRP
900 MHz Compliance (150 mW)
FCC ID TGUDX80 - This device complies with FCC Part 15, Subpart C,
15.247
IC: 7044A-DX8009
2.4 GHz Compliance
FCC ID UE300DX80-2400 - This device complies with FCC Part 15,
Subpart C, 15.247
ETSI/EN: In accordance with EN 300 328: V1.7.1 (2006-05)
IC: 7044A-DX8024
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Link Timeout
Gateway: Configurable via User Configuration Tool (UCT) software
Node: Defined by Gateway
Discrete Inputs
Rating: See control drawing
Sample/Report Rates: DIP switch configurable
Discrete Input ON Condition
PNP: Greater than 8 V
NPN: Less than 0.7 V
Discrete Input OFF Condition (DX99 Models)
PNP: Less than 4.5 V
NPN: Greater than 2.2 V or open
Analog Input Rating (mA Models)
Rating for 4 to 20 mA models: 24 mA
Impedance: Approx. 20 Ohms
Analog Input 1 Sample/Report Rates: DIP switch configurable
Analog Input 2 Sample/Report Rates: 1 second / 16 seconds
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
Analog Input Rating (V Models)
Rating for 0 to 10V models: 10 V
Impedance: Approx. 20 Ohms
Analog Input 1 Sample/Report Rates: DIP switch configurable
Analog Input 2 Sample/Report Rates: 1 second / 16 seconds
Accuracy: 0.25% of full scale +0.01% per °C
Resolution: 12-bit
To verify the analog input's impedance, use an Ohm meter
to measure the resistance between the analog input
terminal (AIx) and the ground (GND) terminal.
Supply Voltage
3.6 V dc low power option from an internal battery
Power Consumption
Consumption: Application dependant
Housing
Glass and cast aluminium w/ chromating and chemically resistant paint
(outside only)
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Interface
Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD
Wiring Access
Two 1/2-inch NPT ports, one 3/4-inch NPT port (internal threads)
Environmental Rating
IEC IP68 2
Operating Conditions3
−
40 °C to +65 °C (
−
40 °F to +149 °F) (Electronics);
−
20 °C to +80
°C (
−
4 °F to +176 °F) (LCD)
95% maximum relative humidity (non-condensing)
Radiated Immunity: 10 V/m, 80-2700 MHz (EN61000-6-2)
Shock and Vibration
IEC 68-2-6 and IEC 68-2-27
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
Certifications
CSA: Class I, Division 1, Groups A, B, C, D; Class II, Division 1,
Groups E, F, G; Class III, Division 1 (Ex ia IIC T4 / AEx ia IIC T4)
Certificate: 2008243
LCIE/ATEX: Zone 0 (Category 1G) and 20 (Category 1D),
Temperature Class T4 (II 1 GD / Ex ia IIC T4 / Ex iaD 20 IP68 T82°C)
Certificate: LCIE 08 ATEX 6098 X
Special Conditions for Safe Use imposed by Intrinsic Safety Certificate
LCIE 08 ATEX 6098 X: Ambient temperature range is –40 to 70 °C.
SureCross
®
DX99 FlexPower devices can only be connected to
Intrinsically Safe certified equipment or simple apparatus as defined by
EN 60079-11. All connected equipment must comply with the Entity
Parameters (Safety Parameters) listed in the
(p/n
141513). The device must only use a lithium battery manufactured by
XENO, type XL-205F.
Metal Housing Dimensions
The metal housing is used for the DX99...D models.
1 Radio range is with the 2 dB antenna that ships with the product. High-gain antennas are available, but the range depends on the environment and line of
sight. To determine the range of your wireless network, perform a Site Survey.
SureCross Wireless I/O Networks Instruction Manual
(p/n 132607) for installation and waterproofing instructions.
3 Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.
SureCross DX99 FlexPower Node (Metal Housing)
P/N 142497 Rev. L
www.bannerengineering.com - Tel: +1-763-544-3164
11