DXM1200-X2 Controller Instruction Manual
© Banner Engineering Corp. All rights reserved.
26
Discrete bit-packed registers for inputs and outputs
Inputs
Outputs
Modbus Register Address
(Decimal)
Description (Inputs)
Modbus Register Address
(Decimal)
Description (Outputs)
6601–6603
Status for all devices
6611–6613
Input 1 from all devices
6691–6693
Output 1 from all devices
6621–6623
Input 2 from all devices
6701–6703
Output 2 from all devices
6631–6633
Input 3 from all devices
6711–6713
Output 3 from all devices
6641–6643
Input 4 from all devices
6721–6723
Output 4 from all devices
6651–6653
Input 5 from all devices
6731–6733
Output 5 from all devices
6661–6663
Input 6 from all devices
6741–6743
Output 6 from all devices
6671–6673
Input 7 from all devices
6751–6753
Output 7 from all devices
6681–6683
Input 8 from all devices
Status registers
(6601–6603) contain a bit-packed representation defining the devices that are operational in the wireless
system. Each bit indicates Node in Sync (1) or Node Not in Sync (0).
A one (1) written to the Discrete Status Register area indicates the device is active within the wireless system. A zero (0)
indicates the device is not active within the wireless network.
Input registers from all devices use Modbus registers 6611 through 6683 to organize the least significant bit into a sequential
array of registers. The first register contains the least significant bit from the input values for the Gateway through Node 15.
The second register contains the input values for Node 16 through Node 31, and the third register contains the input values
for Nodes 32 through 47.
For discrete inputs, only the least significant bit is used. For analog inputs, the least significant bit indicates if the analog
value is above or below the selected threshold value (when using the threshold parameter configured in the User
Configuration Software). For example, a least significant bit of one (1) indicates the analog value is above the selected
threshold value. A least significant bit of zero (0) indicates the analog value is below the threshold value.
Output registers from all devices use Modbus registers 6691 through 6753 to organize the least significant bit into a
sequential array of registers. Output 8 (I/O point 16) cannot be written using the discrete format.
Analog 16-Bit Registers (Registers 6801 through 9098)
The most efficient way to read (or write) analog data from a Gateway is by using these 16-bit analog registers. Most networks
consist of similar Nodes reporting data using the same I/O registers for each Node. For this reason, the analog data is
arranged by I/O point using Modbus registers 6801 through 9098.
For example, Input 1 for Gateway and all Nodes is stored in the first 48 contiguous blocks of 16-bit analog registers,
beginning with register 6801.
In this format, users can read a 16-bit holding register for all devices or write to a register for all devices using one Modbus
message. Using these registers is the most efficient way to read all status registers, read all analog inputs, or write all analog
outputs.
The following registers contain analog I/O values for the Gateway and all Nodes. Values are stored first for the Gateway, then
for each Node in order of Node address.
Analog input and output registers
Inputs
Outputs
Modbus Register Address
(Decimal)
Description (Inputs)
Modbus Register Address
(Decimal)
Description (Outputs)
6801
Input 1 for Gateway
8001
Output 1 for Gateway
6802
Input 1 for Node 1
8002
Output 1 for Node 1
6803
Input 1 for Node 2
8003
Output 1 for Node 2
...
...
...
...
Continued on page 27
Summary of Contents for DXM1200-X2
Page 4: ...4 Warnings 81 Banner Engineering Corp Limited Warranty 82 Document Information 82...
Page 20: ...20...
Page 28: ...28...
Page 36: ...36...
Page 44: ...44...
Page 62: ...62...
Page 70: ...70...
Page 72: ...72...
Page 83: ...LinkedIn Twitter Facebook 2024 All rights reserved www bannerengineering com...