February 02, 2024
DXM1200-X2 Controller Instruction Manual
© Banner Engineering Corp. All rights reserved.
49
Controller
Displays the date, build, model, and serial number.
Ethernet
Displays the IP address, MAC address, DHCP, Gateway
address, and DNS settings.
ISM Radio
Displays the serial number, model, date, firmware part
numbers, and version numbers.
LCD Board
Displays the serial number, model, date, firmware part
numbers, and version numbers.
Push
Shows the current parameters loaded from the XML
configuration that applies to pushing data to a webserver,
including method (Ethernet or cellular), interval, URL, page,
HTTPS, and site ID.
Script
Displays the name of the ScriptBasic file running.
Wi-Fi
Displays the Wi-Fi IP address and other settings.
Display Lock
Display Lock protects the DXM LCD menu system from being used until the proper passcode is entered.
Display Lock menu
Display Lock
Enter password
>> x
to change the value
to accept
ENTER
BACK
to return to the previous menu
↑
↓
The display lock feature uses the configuration software to set a passcode within the DXM. A valid passcode is 1 to 9 digits
long and uses numbers 0 through 9. For example,
1234
or
209384754
.
DXM1200-X2 Modbus Registers for the LCD (Modbus ID 201)
Control the four bi-color LEDs using the display's Modbus registers. Using write maps or ScriptBasic, write the Modbus
registers shown below with 0 (off) or 1 (on).
Modbus registers for the LCD board (Modbus ID 201)
Modbus Register
LED
Color
State
1102 : bit 0
LED 1
Red
1 = On
0 = Off
1103 : bit 0
LED 2
Green
1104 : bit 0
LED 3
Blue
1105: bit 0
LED 4
Amber
1106: bit 0
Backlight
Modbus registers for the RGB indicator
Modbus Registers
Colors
Group A
Group B
Off
Blue
Green
Teal
Red
Violet
Yellow/Green
White/Blue
1107
1110
0
1
0
1
0
1
0
1
1108
1111
0
0
1
1
0
0
1
1
1109
1112
0
0
0
0
1
1
1
1
The primary DXM1200 light is created by two sets of three grouped LEDs (blue, green, and red).
One set of blue LEDs is controlled with register 1107 and another set of blue LEDs is controlled by register 1110.
One set of green LEDs is controlled with register 1108 and another set of green LEDs is controlled by register 1111.
One set of red LEDs is controlled with register 1109 and another set of red LEDs is controlled by register 1112.
Summary of Contents for DXM1200-X2
Page 4: ...4 Warnings 81 Banner Engineering Corp Limited Warranty 82 Document Information 82...
Page 20: ...20...
Page 28: ...28...
Page 36: ...36...
Page 44: ...44...
Page 62: ...62...
Page 70: ...70...
Page 72: ...72...
Page 83: ...LinkedIn Twitter Facebook 2024 All rights reserved www bannerengineering com...