Table 4: D-coded industrial Ethernet connector
4-pin Industrial Ethernet Connector
(female)
Pin
Wire Color
Description
1
4
3
2
1
Black (bk)
+Tx
2
Red (rd)
+Rx
3
Green (gn)
–Tx
4
White (wh)
–Rx
3.2 Configuration Instructions
3.2.1 DXM Configuration Software
Configure the DXMR90-4K using the configuration
. Use this software to customize your configuration and to
process data from the Controller.
Download the latest version of all configuration software from
http://www.bannerengineering.com
. For more information on
using the DXM Configuration Software, refer to the instruction manual (p/n
Figure 4. Overview of the configuration software features
Ethernet
DXM Configuration Software
Local Registers
Register
View Utility
System
Settings
Register Mapping
Scheduler
Action Rules
Script Basic
XML Config File
The configuration software creates an XML file that is transferred to the DXM using an Ethernet connection. The DXM can
also receive the XML configuration file from a Web server using an Ethernet connection. This configuration file governs all
aspects of the DXM operation. The DXM Configuration Software allows the user to define parameters for the DXMR90-4K,
then saves the configuration in an XML file on the PC.
After the configuration file is saved, upload the XML configuration file to the DXMR90-4K for operation.
Important:
The DXMR90-4K IO-Link Master comes preloaded with a default configuration XML file. You
can download the default XML on the product page for the DXMR90-4K.
This quick start guide outlines the basic operations to set up a DXMR90-4K using the configuration software. For a more
comprehensive explanation of features, refer to the DXM Configuration Software Instruction Manual (p/n
).
DXMR90-4K IO-Link Master
www.bannerengineering.com - Tel: + 1 888 373 6767
9