5-Pin M12/Euro-style Male Quick Disconnect
Integral 5-pin M12/Euro-style male quick disconnect (QD) wiring depends on the model and power requirements of the
device. Not all models can be powered by 10 to 30 V dc and not all models can be powered by 3.6 to 5.5 V dc. Refer to
Specifications to verify the power requirements of your device. For FlexPower devices, do not apply more than 5.5 V to the
gray wire.
5-pin M12/Euro-style (male)
Pin
Wire Color
Powered by 10 to 30 V dc
Powered by Battery or Battery Pack
1
4
5
3
2
1
Brown
10 to 30 V dc
2
White
3
Blue
dc common (GND)
dc common (GND)
4
Black
5
Gray
3.6 to 5.5 V dc
Terminal Blocks
Refer to the Class I Division 2/Zone 2 control drawings (p/n
) for wiring specifications or limitations.
IP67 Housing (P2 Models)
IP20 Housing (P2C Models)
G B − W +
A1
A2
GND
PWR
PWR
GND
AO2
AO1
DO4
DO3
DO2
DO1 DI1
DI2
DI3
DI4
AI1
AI2
G
B
−
W
+
DO4
TX/+
RX/
−
DO3
V+
AO2
AO1
DO2
DO1
DI2
DI1
AI2
AI1
V
−
V+
V
−
DI3
DI4
A1
A2
AIx or Ax. Analog IN x
AOx. Analog OUT x
DIx. Discrete IN x
DOx. Discrete OUT x
GND. Ground/dc common connection
PWR. 10 to 30 V dc power connection
RX/-. Serial communication line for the Gateway. No
connection for Nodes
TX/+. Serial communication line for the Gateway; no
connection for Nodes
V+. 10 to 30 V dc power connection
V–. Ground/dc common connection
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the
communication pins (Tx/Rx) causes permanent damage. For FlexPower devices, do not apply more than 5.5 V to the B+
terminal.
Terminal Label
Gateway and DX85
10 to 30 V dc Powered Nodes
Battery Powered Nodes
V+
10 to 30 V dc
10 to 30 V dc
Tx/+
RS485 / D1 / B / +
V–
dc common (GND)
dc common (GND)
dc common (GND)
Rx/–
RS485 / D0 / A / -
B+
3.6 to 5.5 V dc
Wiring Diagrams for Discrete Inputs
Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the
wiring diagram refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board. To power
the sensor using the switch power output (SPx), replace the PWR with SPx in these wiring diagrams.
Sure Cross
®
Performance Node
P/N 155862 Rev. G
www.bannerengineering.com - Tel: +1-763-544-3164
5