background image

Wiring Diagrams for Discrete Inputs

Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.

Discrete Input Wiring for PNP Sensors

Discrete Input Wiring for NPN Sensors

DIx

PWR

10-30V dc

DIx

GND

dc common

Wiring Diagrams for Discrete Outputs

Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.

Discrete Output Wiring (PNP)

DOx

GND

PWR

10-30V dc

Load

dc common

LED Behavior for the Nodes

After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.

LED 1

LED 2

Node Status

 (flashing green)

Radio Link Ok

 (flashing red)

 (flashing red)

Device Error

 (flashing red, 1 per 3 sec)

No Radio Link

Modbus Register Table

I/O #

Modbus Holding Register

I/O Type

I/O Range

Holding Register Rep-
resentation

Terminal

Block Labels

Gateway

Any Node

Min. Value Max. Val-

ue

Min.
(Dec.)

Max. (Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Discrete IN 3

0

1

0

1

DI3

4

4

4 + (Node# × 16)

Discrete IN 4

0

1

0

1

DI4

...

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

 

 

SureCross DX80 Node

4

www.bannerengineering.com - tel: 763-544-3164

P/N 131293 Rev. F

Summary of Contents for SureCross DX80

Page 1: ...r death This device does not include the self checking redundant circuitry necessary to allow its use in personnel safety applications A sensor failure or malfunction can cause either an energized or...

Page 2: ...l DIP Switches To access the internal DIP switches follow these steps 1 Unscrew the four screws that mount the cover to the bottom housing 2 Remove the cover from the housing without damaging the ribb...

Page 3: ...ble system behavior Following a radio link time out all outputs linked to the Node in question are set to de energize discrete outputs to zero analog outputs to 0 mA or 4 mA energize discrete outputs...

Page 4: ...ring up and binding the Gateway and its Nodes verify all devices are communicating properly A Node will not sample its inputs until it is communicating with its Gateway When testing communication betw...

Page 5: ...rform a Site Survey Power Requirements 10 to 30V dc Outside the USA 12 to 24V dc 10 See UL section below for any applica ble UL specifications Consumption Less than 1 4 W 60 mA at 24V dc Housing Polyc...

Page 6: ...X80 C models Warnings Antenna Installations Install and properly ground a qualified surge suppressor when installing a remote antenna system Remote antenna configurations installed without surge suppr...

Page 7: ...FITNESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engine...

Reviews: