22
P/N 134421
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
SureCross™ DX80 Web Configurator
Instruction Manual
RF Devices Tab
Setting
Gateway
Gateway
Pro
Ethernet
Bridge
DX80 is Modbus/TCP
Client/Server (default)
Slave
Master
Master
Default mode. The Gateway is a Modbus slave device and the Ethernet
Bridge is the master device.
DX80 is Modbus RTU
Master
Master
Master
Ignored
The Ethernet Bridge can only communicate with a slave device. In
this mode, any communications sent to the Bridge from the Web
Configurator is ignored. To resume communications, cycle power to the
Gateway. When power is cycled, the Ethernet Bridge begins again as a
master device until the timeout lapses.
DX80 is Modbus RTU
Slave
Slave
Slave
Ignored
Similar to the default mode, but a device other than the Ethernet
Bridge acts as the Modbus master device. The Ethernet Bridge still
communicates with the Gateway and can read and write to registers, but
another device is the master device.
Node 1
Registers 17-32
Node 2
Registers 33-48
Node 3
Registers 49-64
DX80 Gateway
Registers 1-16
Slave ID 1
DX83 Ethernet Bridge
DX80 is Modbus/TCP Client/Server (default)
The default configuration is DX80 is Modbus/TCP Client/Server. The DX83 Ethernet Bridge is
the Modbus master device and only communicates with the device configured as Slave ID 1: the
Gateway.
Send button: After making changes to parameters on the expanded
Configure Point
screen, click on
the Send button to send these changes to the device and click on the Change button to send the
changes to the DX83 Ethernet Bridge or the Gateway Pro.