P/N 134421
6
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
SureCross™ DX80 Web Configurator
Instruction Manual
Advanced Tab
Events
All threshold rules defined under
System > Action Rules > Thresholds
are listed on the
Events
page.
E-mail notification may be selected for each threshold on the occurrence of a true, false, or both.
Use the checkboxes to select which of the three recipients groups to notify. In the sample screen
shot, e-mail recipient 1 will be notified when the system starts up.
Carefully evaluate analog data before enabling automatic e-mail generation. A threshold without
hysteresis and/or minimum times may generate several e-mails per second when the measured
parameter hovers near the threshold limit.
E-mail Acknowledgement: Selecting the Expect Ack checkbox allows the DX80 device to
check incoming e-mail for a reply to the event notification e-mail. Replies must contain an
acknowledgement code in the message. When the acknowledgement is received, e-mail repeating
is cancelled to all recipients.
The expected acknowledgement code is included in the outgoing notification e-mail. A typical
notification code may look like
!08052012R1!
and must be included in the reply in exactly the same
form, including the exclamation points. Replying and sending the e-mail from within the e-mail
program is sufficient as long as the e-mail reply includes the original message.
Repeat Time: The Repeat Time is the rate at which the e-mail is repeated and is given as D,HH:
MM for days,hours:minutes. There should be no embedded spaces between days and hours, only
a comma. If set to zero, and a single 0 will suffice, repeating is disabled. E-mails are only repeated
for Notify on True. Notify on False messages are not repeated unless the threshold rule goes true,
then false again.
System Start-Up: Notification on System Start-Up is a pre-defined event and only repeats
if Expect Ack is checked. If unacknowledged, it will not be repeated and the repeat time is
disregarded.
Other Commands
Prev and Next buttons: Use the Prev and Next buttons to scroll through the list of events if the
events list requires more than one page.
Update button: Sends new data or settings to the Ethernet Bridge or Gateway Pro.