SureCross™ DX80 Quick Start Guide

P/N 128185 Rev A

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com  •  Tel: 763.544.3164

10

Quick Start: 

STEP 6 

> Installation

Ideal Mounting Conditions

Avoid Direct Sunlight

To minimize the damaging effects of 
ultra-violet radiation, avoid mounting the 
Gateway or Node facing intense direct 
sunlight. 

Mount the DX80 within a protective 
enclosure,
Mount the DX80 under an overhang 
or other source of shade,
Install the DX80 indoors, or
Face the unit north when installing 
outside.

Avoid Collecting Rain

When possible, mount the DX80 where 
rain or snow will drain away from the unit. 

Mount the units vertically so that 
precipitation, dust, and dirt do not 
accumulate on permeable surfaces.
Avoid mounting the units on 

fl

 at or 

concave surfaces, especially if the 
display will be pointing up.

Reduce Chemical Exposure

Before installing the DX80 units in a 
chemically harsh environment, contact 
Banner for more information regarding 
the life-expectancy. Solvents, oxidizing 
agents, and other chemicals will damage 
the DX80.

Minimize Mechanical Stress

While the DX80 is very durable, it is a 
sophisticated electronic device that is 
sensitive to shock and excessive loading.

Avoid mounting the units to an object 
that may be shifting or vibrating 
excessively. High levels of static force 
or acceleration may damage the 
housing or electronic components.
Do not subject the DX80 to external 
loads. Do not step on the DX80 or use 
it as a handgrip.
Do not allow long lengths of cable to 
hang from the DX80 glands. Cabling 
heavier than 100 grams should be 
supported instead of allowed to hang 
from the DX80 housing.


Summary of Contents for SureCross DX80

Page 1: ...e transmission path The Gateway receives a transmission from one Node and forwards it to another Node positioned to avoid the obstacle Host connected systems can contain up to 15 nodes within a single...

Page 2: ...s chosen Push Button 2 Double click to select a menu and to enter manual scrolling mode Double click to move up one level at a time LED 1 and 2 Provide real time feedback to the user regarding RF link...

Page 3: ...strial DX80 housing meets IEC IP67 standards Mounting Hole 10 M5 Clearance Mounting Holes accept metric M5 or UNC UNF 10 hardware DIN rail mount adapter bracket available Wiring Terminal Strip Wiring...

Page 4: ...D SAVESNEW VALUES CUR XX Single click Button 2 Single click Button 2 ADJUSTROTARY SWITCHES TOSET SLAVEID SAVESNEW VALUES NID SLID BAUD PRTY Network ID Slave ID Baud Rate Parity Single click B1 NEW XX...

Page 5: ...ouble click Btn 2 NEW XX Single click Button 2 Single click Button 2 SAVESNEW VALUES NADR Node Address NOD XX EC XX IGNORE ERROR Single click Button 1 LCD will display NO ERR if no error is detected S...

Page 6: ...hexidecimal 0 F On the Gateway set the Right Rotary Switch to 0 A Device Address of 0 on the Gateway will display settings for the Gateway itself To view settings for another device on the network adj...

Page 7: ...e is Gateway Device Address 0 Indicates the current status of the I O The display cycles through each I O point of the device then returns to RUN Apply power This reading occurs only when power is app...

Page 8: ...LED 2 flashes Red When communication is established the Node s LED 1 flashes Green Status LED 1 LED 2 Power ON Green ON System Error Red Flash Red Flash Modbus Communication Active Yellow Flash Modbus...

Page 9: ...ble install all devices in positions that optimize the percentage of YELLOW and GREEN data packets received Examine reception readings M R Y G of the Gateway at various locations Note that the numbers...

Page 10: ...le surfaces Avoid mounting the units on flat or concave surfaces especially if the display will be pointing up Reduce Chemical Exposure Before installing the DX80 units in a chemically harsh environme...

Page 11: ...loosely and Pushed against the flanged cover When removing or closing the rotary switch access cover manually twist the cover into position Do not allow cross threading between the cover and the DX80...

Page 12: ...ically for optimal RF communication If necessary consider changing the height of the DX80 position to improve reception levels A wireless network can be hindered by radio interference and obstructions...

Page 13: ...e o ring when it is damaged discolored or showing signs of wear The o ring should be Seated firmly against the threads without stretching to fit or without bulging loosely and Pushed against the flang...

Page 14: ...of the battery holder mounted within the case After replacing the battery allow up to 60 seconds for the device to power up When removing the battery press the battery towards the negative terminal to...

Page 15: ...shown below The following procedure is necessary to change the Gateway Slave ID Baud Rate and Parity Parameter Description Slave ID Default 1 Defines the slave number 01 99 for the serial Modbus RTU p...

Page 16: ...19200 Single click Gateway push button 2 to save the new setting Single click Gateway push button 1 to move to the next field the PARITY field Single click Gateway push button 2 to display the current...

Page 17: ...annerengineering com Tel 763 544 3164 SureCross DX80 Quick Start Guide 17 DX80 Gateway and Node Dimensions 65 0 mm 2 56 65 0 mm 2 56 80 3 mm 3 16 80 8 mm 3 18 60 mm 2 36 120 mm 4 72 127 mm 5 19 mm 0 7...

Page 18: ...f each Node on the network If after a specified number of sequential polling cycles the Node does not acknowledge a message the Gateway considers the link with the Node timed out LCD displays on both...

Page 19: ...devices After any system parameter changes cycle power to cause the devices to resync with the network If a Node device loses synchronization with the network it is programmed to try to acquire sync...

Page 20: ...ling mode within RUN to freeze the I O status on the LCD display for the device in question Verify that when the input device changes state or changes value the LCD mirrors the behavior Also verify th...

Page 21: ...X80 BWA HW 003 Tape PFTE Sealant BWA HW 004 Screws Cover Mount 8 32 x 3 4 18 8 SS Power DX81 Battery Pack Kit DX81 with mounting hardware DX121 Battery Pack Kit DX121 6 cells BWA BATT 001 Replacement...

Page 22: ...rdance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does c...

Page 23: ...and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular...

Page 24: ...ring the warranty period This warranty does not cover damage or liability for the improper application of Banner products This warranty is in lieu of any other warranty either expressed or implied CAU...

Reviews: