background image

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register Rep-
resentation

Terminal

Block Labels

Gateway /

DX85

Any Node

Min.

Max.

Min. (Dec.) Max.

(Dec.)

3

3

3 + (Node# × 16)

Analog IN 3

mA / V

0.0

20.0 / 10.0

0

65535

AI3

4

4

4 + (Node# × 16)

Analog IN 4

mA / V

0.0

20.0 / 10.0

0

65535

AI4

...

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

Analog OUT 1

mA / V

0.0

20.0 / 10.0

0

65535

AO1

10

10

10 + (Node# × 16)

Analog OUT 2

mA / V

0.0

20.0 / 10.0

0

65535

AO2

11

11

11 + (Node# × 16)

Analog OUT 3

mA / V

0.0

20.0 / 10.0

0

65535

AO3

12

12

12 + (Node# × 16)

Analog OUT 4

mA / V

0.0

20.0 / 10.0

0

65535

AO4

...

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

Specifications

Radio and General

Range

900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)

Transmit Power

900 MHz: 21 dBm (150 mW) conducted
2.4 GHz: 18 dBm (65 mW) conducted, less than or
equal to 20 dBm (100 mW) EIRP

900 MHz Compliance (150 mW Radios)

FCC ID TGUDX80 - This device complies with FCC
Part 15, Subpart C, 15.247
IC: 7044A-DX8009

2.4 GHz Compliance

FCC ID UE300DX80-2400 - This device complies with
FCC Part 15, Subpart C, 15.247
ETSI/EN: In accordance with EN 300 328: V1.7.1
(2006-05)
IC: 7044A-DX8024

Spread Spectrum Technology

FHSS (Frequency Hopping Spread Spectrum)

Link Timeout

Gateway: Configurable
Node: Defined by Gateway

Radio range is with the 2 dB antenna that ships with the product.
High-gain antennas are available, but the range depends on the
environment and line of sight. To determine the range of your wire-
less network, perform a Site Survey.

Power

Requirements: +10 to 30V dc (Outside the USA: +12 to
24V dc, ±10%). (See UL section below for any applica-
ble UL specifications)
Consumption: Less than 1.4 W (60 mA) at 24V dc

Housing

Polycarbonate housing and rotary dial cover; polyester
labels; EDPM rubber cover gasket; nitrile rubber, non-
sulphur cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)

Antenna Connection

Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)

Interface

Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD

Wiring Access

Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector

For European applications, power the DX80 from a Limited Power
Source as defined in EN 60950-1.

 

 

SureCross DX80 Gateway

6

www.bannerengineering.com - tel: 763-544-3164

P/N 136325 Rev. F

Summary of Contents for SureCross DX80G9M6S0P0V4V4C

Page 1: ...ian Electrical Code or applicable local codes regulations see Specifications Models Frequency Environmental Rating I O DX80G9M6S0P0V4V4 900 MHz ISM Band IP67 NEMA 6 Inputs Four 0 to 10V analog Outputs...

Page 2: ...n gineering com wireless Setting Up Your Wireless Network To set up and install your wireless network follow these steps 1 Configure the DIP switches of all devices 2 Connect the sensors to the SureCr...

Page 3: ...m of 16 devices Extended address mode uses a security code to bind Nodes to a specific Gateway Bound Nodes can only send and receive informa tion from the Gateway to which they are bound In extended a...

Page 4: ...dc common GND dc common GND dc common GND Rx RS485 D0 A B 3 6 to 5 5V dc Terminal Blocks Connecting dc power to the communication pins will cause permanent damage Do not exceed analog input ratings fo...

Page 5: ...should be at least two meters apart or the communications may fail LED 1 LED 2 Gateway Status solid green Power ON flashing red flashing red Device Error flashing yellow Modbus Communication Active f...

Page 6: ...247 ETSI EN In accordance with EN 300 328 V1 7 1 2006 05 IC 7044A DX8024 Spread Spectrum Technology FHSS Frequency Hopping Spread Spectrum Link Timeout Gateway Configurable Node Defined by Gateway Rad...

Page 7: ...waterproofing instructions Op erating the devices at the maximum operating conditions for exten ded periods can shorten the life of the device Certifications DX8x C External Wiring Terminal Models CS...

Page 8: ...to change Banner reserves the right to modify product specifications or to update docu mentation at any time For the most recent version of any documentation refer to www bannerengineering com 2006 20...