3. Apply power to all devices.
4. Form the wireless network. For binding instructions, refer to the product manual.
5. Observe the LED behavior to verify the devices are communicating with each other.
6. Conduct a site survey between the Gateway and Nodes. For site survey instructions, refer to the product manual.
7. Install your wireless sensor network components. For installation instructions, refer to the product manual.

For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso-
ries, refer to one of the following product manuals.

• SureCross Quick Start Guide: Banner part number 

128185

• SureCross Wireless I/O Network Manual: 

132607

• Web Configurator Manual (used with "Pro" and DX83 models): 

134421

• Host Configuration Manual 

132114

Configuring the DIP Switches

Before making any changes to the DIP switch positions, disconnect the power. For devices with batteries integrated into the housing,
remove the battery for at least one minute. DIP switch changes will not be recognized if power isn't cycled to the device.

Accessing the Internal DIP Switches

To access the internal DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing. For integrated battery models (no ribbon cable) and

Class I, Division 2 certified devices (ribbon cable is glued down), skip this step.

4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials.

After making the necessary changes to the DIP switches, place the black cover plate back into position and gently push

into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing pin. Mount the cover back onto the
housing.

DIP Switch Settings

Switches

Device Settings

1

2

3

4

5

6

7

8

Transmit power level: 1 Watt (30 dBm)

OFF*

Transmit power level: 250 mW (24 dBm), DX80
compatibility mode

ON

Temp °Fahrenheit

OFF*

Temp °Celsius

ON

High resolution (0.1 degree) **

OFF*

Low resolution (1 degree)

ON

Discrete sinking inputs

OFF*

Discrete sourcing inputs

ON

Thermocouple, J-Type

OFF*

OFF*

OFF*

OFF*

Thermocouple, B-Type

OFF

OFF

OFF

ON

SureCross Performance FlexPower Node

 

 

P/N 155863_web
Rev. C

www.bannerengineering.com - tel: 763-544-3164

3

Summary of Contents for SureCross Performance DX80N2X1S-P3E FlexPower

Page 1: ...ete list of accessories refer to Banner Engineering s website www bannerengineering com surecross Models Frequency Power Housing I O DX80N9X2S P3 900 MHz ISM Band 10 to 30V dc or battery supply mod ule IP67 NEMA 6 Inputs Two selectable discrete four ther mocouple one thermistor for CJC Outputs One NMOS sinking discrete DX80N9X1S P3E 10 to 30V dc or integrated battery IP54 NEMA 4 DX80N2X2S P3 2 4 G...

Page 2: ...g its Modbus RTU RS 485 connection is a Modbus slave to a Modbus RTU host controller the wireless network may contain up to 47 Nodes in a single wireless network and the Gateway holds the Modbus registers of all wireless devices within the network A Node is a wireless network end point device used to provide sensing capability in a remote area or factory The Node collects data from sensors and com...

Page 3: ... To access the internal DIP switches follow these steps 1 Unscrew the four screws that mount the cover to the bottom housing 2 Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into 3 Gently unplug the ribbon cable from the board mounted into the bottom housing For integrated battery models no ribbon cable and Class I Division 2 certified devices ribbo...

Page 4: ...1600 degrees Fahrenheit or 1600 degrees Celsius switch the DIP switch to the ON position and use low resolution mode In high resolution the device cannot store values larger than 1600 Temperature Units Use the DIP switch to specify if the temperature is stored in degrees Fahrenheit or Celsius The default position is OFF setting the temperature to Fahrenheit For Celsius measurements set this switch...

Page 5: ... OUT x GND Ground dc common connection PWR Power 10 to 30V dc power connection DX80 C Wiring Wiring power to the DX80 C models varies depending the power requirements of the model Terminal Label Gateway DX85 10 to 30V dc Powered Nodes Battery Powered Nodes V 10 to 30V dc 10 to 30V dc Tx RS485 D1 B V dc common GND dc common GND dc common GND Rx RS485 D0 A B 3 6 to 5 5V dc Connecting dc power to the...

Page 6: ... optional 2 RS 485 D1 B RS 232 Tx 3 dc common GND dc common GND 4 RS 485 D0 A RS 232 Rx The BAT connection is a low voltage connection to the internal battery Remove the internal battery if a low voltage source is connected to the BAT terminal When powering the device from the integrated battery the BAT connection must remain open Terminal Block IP54 A4 A1 A3 A2 GND A3 PWR DO1 DI1 A1 A1 A3 A2 A2 A...

Page 7: ...mocouples are available by configuring the Node Thermocouple Range F Range C Type B 212 to 3 272 F 100 to 1 800 C Type C 32 to 4 208 F 0 to 2 320 C Type E 58 to 1 832 F 50 to 1 000 C Type J 292 to 1 382 F 180 to 750 C Type K 292 to 2 282 F 180 to 1 250 C Type L 328 to 1 652 F 200 to 900 C Type N 32 to 2 192 F 0 to 1 200 C Type R 32 to 2 912 F 0 to 1 600 C Type S 32 to 2 642 F 0 to 1 450 C Type T 2...

Page 8: ...m an integrated battery ship from the factory in storage mode to conserve the battery To wake the device press and hold button 1 for five seconds To put any FlexPower or integra ted battery SureCross radio into storage mode press and hold button 1 for five seconds The radio is in storage mode when the LEDs stop blinking but in some models the LCD remains on for an additional minute after the radio...

Page 9: ...risk of explosion if the battery is re placed incorrectly 4 After replacing the battery allow up to 60 seconds for the device to power up Properly dispose of your used battery according to local regulations by taking it to a hazardous waste col lection site an e waste disposal center or other facility qualified to accept lithium batteries As with all batteries these are a fire explosion and severe...

Page 10: ...OFF Condition PNP Less than 5V NPN Greater than 2V or open Thermocouple Inputs Sample Rate 8 seconds Report Rate 32 seconds Accuracy 0 1 of full scale reading 0 8 C Resolution 0 1 C 24 bit A D converter Thermistor used for CJC Model BWA THERMISTOR 001 Accuracy 0 4 C 10 to 50 C Up to 0 8 C 40 to 85 C Resolution 0 1 C 24 bit A D converter Discrete Output Update Rate 1 second ON Condition Less than 0...

Page 11: ... the most recent version of any documentation refer to our website www bannerengineering com 2006 2010 Banner Engineering Corp All rights reserved Banner Engineering Corp Limited Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one year following the date of shipment Banner Engineering Corp will repair or replace free of charge any prod...

Reviews: