The SX requires a manual restart to clear a Start/Restart Interlock condition and resume operation following a stop
command. Internal Lockout conditions also require a manual reset to return to Run mode after the failure has been corrected.
A reset results in the scanner performing all of its startup tests. The scanner will be offline for approximately 40 seconds.
To reset/restart the SX, close the reset/restart switch for 0.5 to 4.5 seconds and then open it. Closing the reset/restart switch
too long causes the sensor to ignore the reset/restart request.
7.3.1 Reset Signal Function
There are two internally controlled states between the stop and restart of the scanner:
•
Interlock ON: Device can be restarted to its normal function because the detected object has been removed from the
Safety Zone
•
Interlock OFF: Device is off because the object has not been removed from the Safety Zone
The Interlock ON will be signaled by the LED 5 (right LED under the device display) turning amber and the display showing
Restart inside a circle.
The manual reset input must be connected to +24 V dc via a Normally Open switch contact.
SX Safety Laser Scanner
100