5/18
Designed for care
Interface
For more information: www.bano.no
NOTE! PLUMBING
Water outlet on left side as shown in illustration.
Placement of stopvalve:
because of moving parts when
adjusting the cistern’s height the stop valve must be placed
exactly as is shown on the illustration.
Stopvalves are turned as shown on drawing.
Concerning water;
finish with stop valve with 1/2” external
threads (G15). (Threads pointing up)
Drainpipe in floor:
Ø110 drainpipe without cuff is finished
40 mm above floor
OBS! RIB:
Loadtested untill 500 kg.
Min.: 48x198 board
Nailingstrips must be placed flush against wall material.
Nailing strips are indicated with shaded area.
NOTE! ELECTRICAL:
Electrical innstallation only for products with electrical height
adjustment.
Electrical outlet on right side as shown in illustration.
Electrical cable/ pipe is pulled 500 mm from wall and placed
200 mm above finished floor and 100 mm from the center of
the cistern’s drain.
Electritian connects IP44-box aftrer the cistern is installed.
(IP44-box not included)
NOTE! ELECTRICAL: This ONLY applies to
cisterns with electric height-adjustment.