Installation & Operating Instructions

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 01/25/18

39021_RCV_900_BACnet

4 of 9

900MHz BACnet Gateway/Receiver 

Gateway Network Setup continued...

DATA TRANSMISSION METHOD

 (Fig 6)

The Gateway can transmit its data 

via various methods, including HTTP 

GET, HTTP POST and BACnet/IP.

HTTP GET: 

To use this option, select 

the radio button next to HTTP GET 

method and enter the Web server 

host, port and URI.  Click the “Save 

Configuration” button to save your updates. 

HTTP POST:

 To use this option, select the radio button next to HTTP POST method and enter the Web server host, 

port and URI. For WAM Remote, use Web server host: https://wam.bapihvac.com, using port: 443 and URI: /api/data. 

For WAM Local, use Web server host: (IP address of computer running the WAM Local application), using port: 9000 

and  URI: /api/data.  Click the “Save Configuration” button to save your updates.

BACnet/IP:

 Select the radio button next to this option, and enter the BACnet device ID that you would like to use. 

BACnet ID can have a value of 1 to 4026531839 and is created using digits 0-9 only.  Click the “Save Configuration” 

button to save your updates.

NO READING TIMEOUT AFTER INTERVAL TIME

 (Fig 7)

This option sets the amount of time the Gateway will wait for a sensor reading 

before it reports to BACnet that the sensor is “out-of-service”. The “out-of-

service” status is shown in the sensor’s “status-flags” variable and the sensor 

is given a temperature value of -200.  If the Transmission Interval of the 

sensors is set at 5 minutes, and the No Reading Timeout After Interval Time is 

set at 10 minutes, then this option will not be activated until 15 minutes after 

the last successful transmission was received.

UPDATED GATEWAY VERSION

 (Fig 8)

BAPI will periodically release updates to the Gateway software. Go to the BAPI 

website and navigate to the Gateway page, then follow instructions to check 

for new software and download it to your local computer.  Once the software is 

downloaded, click the “Choose File” button and use the file browser to select 

the update file.  When the file is selected, its name will show up on the screen.
Once the file is selected, click the “Update Gateway” button.  The update 

will install on the Gateway, and it will reboot automatically so that the changes can take effect. This can take up to 5 

minutes at which point the Gateway will disappear from the Gateway Discovery Tool Screen. It will return once the 

reboot has been successful. 

SET TIME ZONE, DATE AND TIME

 (Fig 9)

The Gateway is set up to use the time and date that are broadcast on 

the network that it is attached to.  If the Gateway time and date are not 

automatically set up, you can make a manual correction to the date and time. 

To do this you must first turn off logging on all devices, then set the Gateway 

time. Once the time is set, device logging can be turned back on where 

needed.
Use the “Time Zone”, “Month, Day, Year”, and “Hour, Minute, Second” pull 

down lists to select the correct time and zone, and then click “Set Zone Date 

Time” to save changes.

Fig. 7: 

No Reading Timeout Interval

           Time

Fig. 8: 

Update Gateway Version

Fig. 9: 

Set Time Zone, Date & Time

Continued from previous page...

Fig. 6: 

Gateway Data Transmission Method

Summary of Contents for GTW900

Page 1: ...f the following browsers to access the Gateway configuration and data screens Web Browsers Supported Microsoft Internet Explorer 7 Mozilla Firefox 11 Apple Safari 5 1 Google Chrome v18 or newer versio...

Page 2: ...oper ethernet connection first before applying power to the Gateway Connect the supplied CAT5 cable to the Ethernet wall jack and to the Gateway Ethernet port When the Ethernet cable is connected the...

Page 3: ...on Turn off the Gateway via the Halt button Log out of the configurator screen via the Logout button Upgrade the Gateway firmware Configure the Time and Date The Gateway contains many user configurabl...

Page 4: ...and the sensor is given a temperature value of 200 If the Transmission Interval of the sensors is set at 5 minutes and the No Reading Timeout After Interval Time is set at 10 minutes then this option...

Page 5: ...alues in that column Sensors Button Click to instantly refresh the sensor readings page The page is refreshed automatically every 30 seconds Delete All Button Clicked to delete all readings that are r...

Page 6: ...It will also show any sensors that have been discovered by the Gateway even though they are reporting to a different Gateway Settings for an ED Device Type will not be added to the settings list if t...

Page 7: ...Gateway to ensure a solid communication link See the installation sheets for each ED device for the location of the Service Button Channel Use the pull down list to select what channels you want the G...

Page 8: ...ning Voltage Use this pull down to select a battery level when the sensor will go into Battery Conservation Mode and stop transmitting sensor readings and start logging them The sensor will continue t...

Page 9: ...equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the...

Reviews: