DESCRIPTION

The CMC-15 is a field installable start kit.  It is a
positive temperature coefficient resistor (PTCR) that
increases starting torque by momentarily increasing the
current to the start winding of the compressor. The
CMC-15 consists of:

1.

PTCR  910-1097

2.

Installation Instructions  7960-245

3.

CMC-15 unit label  7961-312-0009

For use with all WA/WL181 – WA/WL601 Hi-Boy Wall
Mount Heat Pumps and Air Conditioners (“A” Electrical
Versions ONLY).

INSTALLATION INSTRUCTIONS

CMC-15

START  KIT

Bard Manufacturing Company, Inc.
Bryan, Ohio  43506

INSTALLATION INSTRUCTIONS

Disconnect all power to unit.  Remove control panel
inner and outer covers.  Circled numbers on Figure 1
correspond to installation instruction steps.  Dashed
lines indicate that a wire has been disconnected from
this terminal.

Step 1.

Mount start kit (PTCR) in position shown in

Figure 1, Step 1.

Step 2.

Connect wires between terminals (Herm) and

(C) of dual can capacitor as shown in Figure
1,  Step 2.

Step 3.

Recheck wiring.  Refer to Figure 1.

Step 4.

Replace all panels and covers.  This

completes installation.