Manual 2100-701
Page
5 of 16
PERFORMANCE AND APPLICATION DATA – ERV-F*3
Summer Cooling Performance
(Indoor Design Conditions 75°DB/62°WB)
LEGEND:
VLT = Ventilation Load – Total
VLS = Ventilation Load – Sensible
VLL = Ventilation Load – Latent
HRT = Heat Recovery – Total
HRS = Heat Recovery – Sensible
HRL = Heat Recovery – Latent
WVL = Winter Ventilation Load
WHR = Winter Heat Recovery
Winter Heating Performance
(Indoor Design Conditions 70°F DB)
NOTE:
All performance data is based on
operating intake and exhaust blower on
the same speed.
Ambient
OD
Ventilation Rate 400 CFM
63% Efficiency
Ventilation Rate 325 CFM
64% Efficiency
Ventilation Rate 250 CFM
65% Efficiency
DB/
WB
F
VLT
VLS
VLL
HRT
HRS
HRL
VLT
VLS
VLL
HRT
HRS
HRL
VLT
VLS
VLL
HRT
HRS
HRL
105
75
70
65
19080
12960
12960
12960
12960
12960
6120
0
0
12020
8164
8164
8164
8164
8164
3855
0
0
15502
10530
10530
10530
10530
10530
4972
0
0
9921
6739
6739
6739
6739
6739
3182
0
0
11925
8100
8100
8100
8100
8100
3825
0
0
7751
5265
5265
5265
5265
5265
2486
0
0
100
80
75
70
65
60
29080
19080
10980
10800
10800
10800
10800
10800
10800
10800
17280
8280
180
0
0
17690
12020
6717
6804
6804
6804
6804
6804
6804
6804
10886
5216
113
0
0
22815
15502
8921
8775
8775
8775
8775
8775
8775
8775
14040
6727
146
0
0
14601
9921
5709
5616
5616
5616
5616
5616
5616
5616
8985
4305
93
0
0
17550
11925
6862
6750
6750
6750
6750
6750
6750
6750
10800
5175
112
0
0
11407
7751
4460
4387
4387
4387
4387
4387
4387
4387
7019
3363
73
0
0
95
80
75
70
65
60
28080
19080
10980
8640
8640
8640
8640
8640
8640
8640
19440
10440
2340
0
0
17690
12020
6917
5443
5443
5443
5443
5443
5443
5443
12247
6577
1474
0
0
22815
15502
8921
7020
7020
7020
7020
7020
7020
7020
15795
8482
1901
0
0
14601
9921
5709
4492
4492
4492
4492
4492
4492
4492
10108
5428
1216
0
0
17550
11925
6862
5400
5400
5400
5400
5400
5400
5400
12150
6525
1462
0
0
11407
7751
4460
3510
3510
3510
3510
3510
3510
3510
7897
4241
950
0
0
90
80
75
70
65
60
28080
19080
10980
6480
6480
6480
6480
6480
6480
6480
21600
12600
4500
0
0
17690
12020
6917
4082
4082
4082
4082
4082
4082
4082
13608
7938
2835
0
0
22815
15502
8921
5265
5265
5265
5265
5265
5265
5265
17550
10237
3656
0
0
14601
9921
5709
3369
3369
3369
3369
3369
3369
3369
11232
6552
2340
0
0
17550
11925
6862
4050
4050
4050
4050
4050
4050
4050
13500
7875
2812
0
0
11407
7751
4460
2632
2632
2632
2632
2632
2632
2632
8774
5118
1828
0
0
85
80
75
70
65
60
28080
19080
10980
4320
4320
4320
4320
4320
4320
4320
23760
14760
6660
0
0
17690
12020
6917
2721
2721
2721
2721
2721
2721
2721
14968
9298
4195
0
0
22815
15502
8921
3510
3510
3510
3510
3510
3510
3510
19305
11992
5411
0
0
14601
9921
5709
2246
2246
2246
2246
2246
2246
2246
12355
7675
3463
0
0
17550
11925
6862
2700
2700
2700
2700
2700
2700
2700
14850
9225
4162
0
0
11407
7751
4460
1755
1755
1755
1755
1755
1755
1755
9652
5996
2705
0
0
80
75
70
65
60
19080
10980
3780
2160
2160
2160
2160
2160
16920
8820
1620
0
12020
6917
2381
1360
1360
1360
1360
1360
10659
5556
1020
0
15502
8921
3071
1755
1755
1755
1755
1755
13747
7166
1316
0
9921
5709
1965
1123
1123
1123
1123
1123
8798
4586
842
0
11925
6862
2362
1350
1350
1350
1350
1350
10575
5512
1012
0
7751
4460
1535
877
877
877
877
877
6873
3583
658
0
75
70
65
60
10980
3780
0
0
0
0
10980
3780
0
6917
2381
0
0
0
0
6917
2380
0
8921
3071
0
0
0
0
8921
3071
0
5709
1965
0
0
0
0
5709
1965
0
6862
2362
0
0
0
0
6862
2362
0
4460
1535
0
0
0
0
4460
1535
0
Ambient
OD
Ventilation Rate
400 CFM 75% Eff.
325 CFM 76% Eff.
250 CFM 77% Eff.
DB/°F
WVL
WHR
WVL
WHR
WVL
WHR
65
2160
1620
1755
1333
1350
1039
60
4320
3240
3510
2667
2700
2079
55
6480
4860
5265
4001
4050
3118
50
8640
6480
7020
5335
5400
4158
45
10800
8100
8775
6669
6750
5197
40
12960
9720
10530
8002
8100
6237
35
15120
11340
12285
9336
9450
7276
30
17280
12960
14040
10670
10800
8316
25
19440
14580
15795
12004
12150
9355
20
21600
16200
17550
13338
13500
10395
15
23760
17820
19305
14671
14850
11434