background image

Manual    2100-392
Page       6

DUCT WORK

The air distribution system should be designed and
installed in conformance with manuals published by Air
Conditioning Contractors of America (ACCA) as set
forth in Manual D, or ASHRAE publications.

INSTALLING A COOLING UNIT

When the furnace is used in connection with a cooling
unit*, the furnace shall be installed parallel with or on
the upstream side of the cooling unit to avoid
condensation in the heating element.  With a parallel
flow arrangement, the dampers or other means used to
control flow of air shall be adequate to prevent chilled
air from entering the furnace, and if manually operated,
must be equipped with means to prevent operation of
either unit, unless the damper is in the full heat or cool
position.

*

A cooling unit is an air conditioning coil, heat
pump coil or chilled water coil.

When installing a cooling unit above an FH or FL
(below on an FC) series furnace, the coil must be
spaced far enough from the furnace outlet to assure
proper operation of the furnace.  Bard supplied coils,
when used with Bard supplied coil cabinets, are
automatically positioned.

For top discharge FH and FL models, when coils are
installed without using Bard coil cabinets or coils of
another brand are used, the coil drain pan should be
located a minimum of two (2) inches above the top of
the furnace cabinet.  If a greater clearance is specified
by the coil manufacturer then it would apply.

NOTE: If drain pan is anything other than a steel pan

particular attention must be given to the
installation instructions for the coil to make
sure it is acceptable for use with these oil
furnaces having maximum outlet air
temperature of 200° F.

See CFM versus static pressure tables on pages 23-26
for additional information.

IMPORTANT

When a furnace is installed so that supply
ducts carry air circulated by the furnace to
areas outside the space containing the
furnace, the return air must also be handled
by a duct(s) sealed to the furnace casing and
terminating outside the space containing the
furnace  This is to prevent drawing possible
hazardous combustion products into the
circulated air.

INADEQUATE SUPPLY AIR and/or RETURN
AIR DUCT SYSTEMS

Short cycling because of limit control operation can be
created by incorrectly designed or installed supply and/
or return air duct systems.

The duct systems must be designed using ASHRAE or
ACCA design manuals and the equipment CFM and
external static pressure ratings to insure proper air
delivery capabilities.

On replacement installations, particularly if equipment
is oversized, the duct systems can easily be undersized.
Modifications may be required to assure that the
equipment is operating within the approved
temperature rise range when under full rated input
conditions
, and that no short cycling on limit controls is
occurring.

INSTALLING THE FURNACE

A typical installation is shown in Figure 4.  All parts of
the furnace installation (furnace, oil tank and piping
systems, combustion and ventilation air, venting, etc.)
must comply with NFPA31, Installation of Oil Burning
Equipment -- latest edition.  This drawing shows the
typical connecting parts needed to correctly install this
furnace.  Make sure that all parts of the heating system
comply with the local codes.

Check the furnace and your load calculation to verify
that the unit is properly sized.  (Refer to Equipment
Selection” section on Page 2.)

The correct size of unit needed may be substantially
smaller than the unit being replaced due to home
improvements and technology advancements since the
initial installation.

WIRING

FACTORY WIRING

All units are fully factory wired.  Multispeed blowers
are factory wired on high speed for cooling/manual fan
operation.  Heating speeds are wired for the largest
input and may need lower speed for field installed low
input nozzle.  If replacement wire is necessary, use 105
degrees C minimum.  See electrical data, Table 5.

FIELD WIRING

All wiring must conform to the National Electrical
Code and all local codes.  A separate fuse or breaker
should be used for the furnace.

Summary of Contents for FC085D36D

Page 1: ...RY OR DEATH FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE IMPORTANT NOTICE THIS FURNACE IS NOT INTENDED FOR USE AS A...

Page 2: ...ons 3 Figure 2 Hi Boy Models Dimensions 4 Figure 3 Counterflow Models Dimensions 5 Figure 4 Typical Installation Requirement Front Flue 7 Figure 5 Typical Single Inside Tank Installation 8 Figure 6 Pr...

Page 3: ...Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION...

Page 4: ...of the furnace dry and reduce rusting An oil burner must have a generous supply of combustion air to operate properly The flow of combustion and ventilating air must not be obstructed from reaching th...

Page 5: ...a i D H J e z i S o N d e s U D 6 3 D 5 8 0 F L F D 6 3 D 5 8 0 R L F 3 2 3 2 4 1 7 4 4 1 7 4 4 1 0 4 4 1 0 4 0 2 x 2 2 0 2 x 2 2 6 1 x 2 2 6 1 x 2 2 t n o r F r a e R 6 6 4 3 4 1 5 1 x 0 2 x 6 1 1 x...

Page 6: ...C s g n i n e p O m u n e l P G a i D e u l F A h t d i W B h t p e D C t h g i e H E x D y l p p u S H x F 2 n r u t e R 1 e z i S r e t l i F D 6 3 D 5 8 0 H F D 8 4 D 0 1 1 H F D 0 6 D 0 1 1 H F 3...

Page 7: ...P G a i D e u l F A h t d i W B h t p e D C t h g i e H E x D 2 n r u t e R H x F y l p p u S 1 e z i S r e t l i F D 6 3 D 5 8 0 C F 3 2 2 1 9 2 6 5 0 2 x 2 2 9 1 x 8 1 6 0 2 x 0 1 0 2 x 5 1 j Washab...

Page 8: ...be handled by a duct s sealed to the furnace casing and terminating outside the space containing the furnace This is to prevent drawing possible hazardous combustion products into the circulated air...

Page 9: ...F L F 1 0 6 5 1 1 3 7 1 3 1 6 5 7 1 7 1 5 1 5 1 D 6 3 D 5 8 0 R L F 1 0 6 5 1 1 3 7 1 3 1 6 5 7 1 7 1 5 1 5 1 D 8 4 D 0 1 1 F L F 1 0 6 5 1 1 2 2 1 2 1 5 0 1 7 1 7 1 6 1 0 2 D 8 4 D 0 1 1 R L F 1 0 6...

Page 10: ...ls of the highest quality The controls consist of a high voltage Beckett solid state igniter a Beckett CleanCut oil pump with an integral solenoid valve and a Beckett R7184B primary control These cont...

Page 11: ...14 000 volt spark instead of a 10 000 volt spark of the iron core BECKETT R7184B PRIMARY CONTROL The R7184B Interrupted Electronic Oil Primary is a line voltage safety rated interrupted ignition oil...

Page 12: ...On any given call for heat the control will allow three ignition trials After the three trials the control will go into a soft lockout mode The LED will flash 2 seconds on and 2 seconds off when in th...

Page 13: ...es of taking the smoke tests and measuring the CO2 or O2 and flue gas temperature 7 The burner air adjustment shutters are factory set to the recommended start up settings as shown in Table 9 These se...

Page 14: ...securely 10 Measure the stack temperature Subtract the room temperature to obtain the net reading and use the Efficiency Chart Table 8 to determine the steady state efficiency FIGURE 6 PRESSURE GAUGE...

Page 15: ...5 7 9 3 7 6 2 7 7 1 1 6 4 8 8 0 7 8 5 5 8 1 4 8 7 2 8 3 1 8 9 9 7 5 8 7 0 7 7 6 5 7 2 4 7 8 2 7 4 1 7 0 1 1 7 0 8 8 5 6 8 0 5 8 5 3 8 0 2 8 5 0 8 0 9 7 5 7 7 0 6 7 5 4 7 0 3 7 5 1 7 0 0 7 3 0 1 TABLE...

Page 16: ...DE ADJUSTMENTS BURNER NOZZLE AND ELECTRODE ADJUSTMENTS Check nozzle size as to conformance to installation requirements Install nozzle by screwing into hexagon adapter Refer to recommended start up se...

Page 17: ...tal input rating of all appliances shall be provided TABLE 11 SQUARE FEET REQUIRED TO QUALIFY AS UNCONFINED SPACE l a t o T H U T B t u p n I e c a p S d e n i f n o c n U n I a e r A m u m i n i M t...

Page 18: ...BTU per hour 70 square inches per gallon per hour of total input of all appliances in the enclosure FIGURE 9 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS NOTE Each air duct opening sha...

Page 19: ...e inches per gallon per hour of the total input rating of all appliances in the enclosure FIGURE 11 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPACE AN...

Page 20: ...are designed to be controlled with any 24V heating or heating cooling thermostat The heat cool thermostats must be designed for independent heat cool transformer circuits to assure that the 24V transf...

Page 21: ...0 1 0 9 0 6 0 9 0 6 0 0 2 0 0 2 w o L w o L d e M 0 7 1 0 7 1 0 1 1 0 1 1 0 9 0 9 D 6 3 D 5 8 0 F L F 5 6 5 7 0 9 0 6 0 9 0 6 0 0 2 0 0 2 w o L d e M 0 3 2 0 3 2 0 4 1 0 4 1 0 1 1 0 1 1 D 8 4 D 0 1 1...

Page 22: ...counterflow models require a bracket installation and final filter location projects into return air plenum attachment for furnace See Figure 14 Refer to Figure 14 for Lo Boy models which have filters...

Page 23: ...uired in the furnace side and the bottom of the filter rack is aligned over the bottom of the 14 x 23 cutout The top of the filter rack rises approximately 6 inches above the top of the cutout The 3 i...

Page 24: ...is accessible from the rear of the furnace by removing the blower filter access door The electrical switch should be turned off prior to removing the access door Refer to Figure 15 below FIGURE 15 FI...

Page 25: ...e control Following is the method we recommend in checking the safety switch in this primary control A Flame Failure Simulate by shutting off oil supply manual valve while burner is on Within 9 second...

Page 26: ...ndependently from the mounting system to perform basic annual service and inspection The mounting system is completely adjustable so exact alignment between the burner tube and combustion chamber may...

Page 27: ...rom T T on primary control Remove 6 5 16 inch bolts from around front plate Next remove 2 5 16 inch nuts from upper right and left hand corners of the front plate Pull entire assembly straight back aw...

Page 28: ...er and will destroy the chamber Refer to the Cleaning of Furnace section for proper cleaning methods COMMON CAUSES OF TROUBLE CAUTION To avoid accidents always open main switch OFF position when servi...

Page 29: ...00 1200 1300 1400 0 0 1 0 2 0 3 0 4 0 5 External Static Pressure in Inches of Water CFM Standard Airflow HIGH MED LOW FH110D48D System Resistance Curves 800 1000 1200 1400 1600 1800 2000 0 0 1 0 2 0 3...

Page 30: ...ANCE CURVES FH110D60D System Resistance Curves 1000 1200 1400 1600 1800 2000 2200 2400 0 0 1 0 2 0 3 0 4 0 5 External Stactic Pressure in Inches of Water CFM Standard Airflow HIGH MED HIGH External St...

Page 31: ...0 1100 1200 1300 1400 1500 0 0 1 0 2 0 3 0 4 0 5 External Static Pressure in Inches of Water CFM Standard Airflow HIGH MED LOW FLF R110D48D System Resistance Curves 800 1000 1200 1400 1600 1800 2000 0...

Page 32: ...0 3 0 4 0 5 External Static Pressure in Inches of Water CFM Standard Airflow HIGH MED LOW FLR140D60D System Resistance Curves 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 0 0 05 0 1 0 15 0 2 0 2...

Page 33: ...Manual 2100 392 Page 31...

Page 34: ...Manual 2100 392 Page 32...

Page 35: ...Manual 2100 392 Page 33...

Reviews: