background image

Manual     2100-422
Page      25

LOUVERS AND GRILLES

In calculating free area for ventilation and combustion
air requirements, consideration shall be given to the
blocking effect of louvers, grilles, or screens protecting
openings.  Screens used shall not be smaller than 1/4
inch (6.3 mm) mesh and shall be readily accessible for
cleaning.  If the free area through a design of louver or
grille is known, it shall be used in calculating the size
opening required to provide the free area specified.  If
the design and free area is not known, it may be
assumed that wood louvers will have 30-35 percent free
area and metal louvers and grilles will have 60-75
percent free area.

VENTING OPTIONS

This furnace is designed to be vented conventionally
into a vertical chimney or horizontally through a side
wall with an optional Field Controls side wall power
venting system.

Note that the FH, FC and FLF series furnaces have been
designed to allow for bringing the vent system through
the cabinet side for increased venting flexibility.  To
take advantage of this feature, simply remove the
desired knockout from either side or top of unit and
rotate flue box accordingly by removing four (4) screws
under cleanout plate as shown in Figure 4.  Make sure
smoke pipe gasket is in place before reinstalling flue
box screws.

VERTICAL VENTING

If the unit is to be vertically vented make sure the flue
pipe from the furnace to the chimney is the same size
diameter as the flue outlet of the furnace which is 6”.
The flue pipe must have no reductions in diameter, be
made of a corrosion-resistant material having an
upward pitch of 1/4” for every foot of horizontal run,
and be made of material capable of handling
temperatures up to 1800° F.

A barometric damper is supplied with the furnace and
must be installed in the flue pipe observing the
instructions packaged with the damper control.  The
barometric damper opening must be located in the same
atmospheric pressure zone as the combustion air inlet to
the furnace.  The furnace must not be vented into the
same chimney with any solid fuel burning appliance
such as a wood burner or pellet burner.  Masonry
chimneys must be lined with a listed system or other
approved material that will resist corrosion, softening or
cracking from flue gas temperatures up to 1800° F.  See
Standard for Installation of Oil Burning Equipment
NFPA31 latest edition and Standard for Chimneys
NFPA211 latest edition for additional information.

HORIZONTAL VENTING

This furnace is designed to be horizontally vented
through a side wall with an optional side wall power
vent.  The recommended side wall venter is the Field
Controls model number SWG-4HDS for 085 and 110
models, and SWG-5S for 140 models only.  This venter
can be purchased through your local distributor.  Follow
all installation instructions packaged with the venter
system.

THERMOSTAT

These furnaces are designed to be controlled with any
24V heating or heating/cooling thermostat.  The
heat/cool thermostats must be designed for independent
heat/cool transformer circuits to assure that the 24V
transformer built into the oil primary control does not
conflict with the main furnace 24V transformer.  The
heat anticipator should be set at 0.20A.  This is a
nominal setting.  The thermostat circuit should be
checked to verify setting.

Summary of Contents for FH085D36E

Page 1: ...Y INJURY OR DEATH FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE IMPORTANT NOTICE THIS FURNACE IS NOT INTENDED FOR USE...

Page 2: ...Data 34 FIGURES Figure 1 FL R Models Dimensions 3 Figure 2 FH Models Dimensions 4 Figure 3 FC Models Dimensions 5 Figure 4 Typical Unit Setup FLF 8 Figure 5 Typical Flue Installation Requirements FLF...

Page 3: ...Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION...

Page 4: ...burner must have a generous supply of combustion air to operate properly The flow of combustion and ventilating air must not be obstructed from reaching the furnace See Combustion Air Requirements se...

Page 5: ...d i W B h t p e D C t h g i e H E x D y l p p u S F x D n r u t e R n o i t a c o L G a i D H J e z i S o N d e s U E 6 3 D 5 8 0 F L F E 6 3 D 5 8 0 R L F 3 2 3 2 5 2 1 8 4 5 2 1 8 4 5 2 6 6 3 5 2 6...

Page 6: ...FH110 SPECIFICATION SHEET 19 1 4 16 RETURN OPENING CUT OUT OPTIONAL OIL ENTRANCE OIL ENTRANCE FRESH AIR KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE OPTIONAL LOW VOLTAGE ENTRANCE FLUE KNOCKOUT RETURN OPENI...

Page 7: ...RANCE FRESH AIR KNOCKOUT OPTIONAL OIL ENTRANCE OIL ENTRANCE REAR CLEANOUT DOOR OPTIONAL OIL ENTRANCE HIGH VOLTAGE ENTRANCE LOW VOLTAGE ENTRANCE FLUE KNOCKOUT 18 1 8 19 1 8 30 1 2 21 7 8 19 7 8 FLUE KN...

Page 8: ...CFM and external static pressure ratings to insure proper air deliverycapabilities On replacement installations particularly if equipment is oversized the duct systems can easily be undersized Modific...

Page 9: ...m u m i n i M t i u c r i C y t i c a p m A e m i T x a M e s u F y a l e D R C A H r o r e k a e r B t i u c r i C P H A L F P H A L F E 6 3 D 5 8 0 H F 1 0 6 5 1 1 2 9 3 1 5 7 7 1 7 1 5 1 5 1 E 8 4...

Page 10: ...oltage thermostat entrance Shut off switch if not fused power line must include fuse or circuit breaker To power source To thermostat and optional A C unit Air Boot knockout optional Inspection door T...

Page 11: ...t supplied with regulator 90 Rotatable Flue Box on front flue models remove appropriate cabinet knockout Mounting screws located under flue box cover Flue Box Cover L i n e d C h i m n e y Thimble Cle...

Page 12: ...tups must comply with NFPA31 BECKETT AFG OIL BURNER This furnace is equipped with a high static Beckett AFG oil burner which is designed to produce adequate draft in nearly any vertically vented appli...

Page 13: ...to operate and provides additional troubleshooting features to ease service and reduce down time The operational guide for the R7184B primary control is provided following on Page 12 BECKETT SOLID STA...

Page 14: ...flashes More than 1600 and less than 5000 ohms Burner Option Flame Quality Monitor This control is trained to recognize and remember a good flame based on initial burner set up Control then monitors...

Page 15: ...IONS OIL PRIMARY T T CONNECTIONS LINE VOLTAGE CONNECTION HOT UNUSED BLOWER MOTOR SPEED CONNECTIONS LINE VOLTAGE CONNECTION COM L2 ELECTRIC AIR CLEANER CONNECTION HUMIDIFIER CONNECTION HEATING BLOWER S...

Page 16: ...wheel are clear of dirt and lint Seal any air leaks into the combustion chamber D Nozzle Inspection Annual replacement of nozzle is recommended The nozzle size should match the design load DO NOT OVE...

Page 17: ...are enough to establish the curve In adjusting each air setting it is helpful to note the various positions of air gate at which measurements are made so that the final setting can be located quickly...

Page 18: ...ed thus causing oil to drip into the combustion chamber after shutdown If poor cutoff persists repair or replace pump Also make sure the pump solenoid is working If not replace SHORT FORM ADJUSTMENT P...

Page 19: ...stment range 0 2 4 6 8 8 10 12 14 6 Knee Best air setting Plotted point Plotted point Plotted point CO Curve from plotted points 2 Air Settings Low High Bacharach Smoke Number Percent CO in Flue Gas 2...

Page 20: ...Manual 2100 422 Page 18 FIGURE 9 PRESSURE GAUGE CONNECTION TO BLEED PORT MIS 1660 Pressure Gauge Remove Bleed Port to attach pressure guage...

Page 21: ...1 1 7 0 8 8 5 6 8 0 5 8 5 3 8 0 2 8 5 0 8 0 9 7 5 7 7 0 6 7 5 4 7 0 3 7 5 1 7 0 0 7 3 0 1 TABLE 7 RECOMMENDED START UP SETTINGS j 70 degree hollow cone spray pattern 100 PSIG pump pressure e c a n r u...

Page 22: ...fficient supply of combustion air is available for the complete combustion of the fuel oil Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fue...

Page 23: ...RNER ASSEMBLY REMOVE PUMP TO ASSEMBLE INNER AIR BOOT USE THIS KNOCKOUT FOR OIL LINE INSERT OUTER AIR BOOT AND SECURE FLANGE TO UNIT MAKE ALL SETTINGS ACCORDING TO MANUAL FOR AIR BOOT REMOVE KNOCKOUT I...

Page 24: ...shall be provided For combustion air options see Page 20 Combustion Air Requirements MIS 1336 NOTE Each opening shall have a free area of not less than one square inch per 1 000 BTU per hour 140 squa...

Page 25: ...70 square inches per gallon per hour of total input of all appliances in the enclosure FIGURE 13 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS NOTE Each air duct opening shall have a fr...

Page 26: ...e inches per gallon per hour of the total input rating of all appliances in the enclosure FIGURE 15 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPACE AN...

Page 27: ...corrosion resistant material having an upward pitch of 1 4 for every foot of horizontal run and be made of material capable of handling temperatures up to 1800 F A barometric damper is supplied with...

Page 28: ...o L w o L d e M E 6 3 D 5 8 0 F L F 5 5 5 6 5 7 0 9 0 6 0 9 0 6 0 9 0 6 0 0 2 0 0 2 0 0 2 w o L w o L d e M E 8 4 D 0 1 1 F L F 5 8 0 0 1 0 9 0 6 0 9 0 6 0 0 2 0 0 2 w o L d e M h g i H d e M E 0 6 D...

Page 29: ...pe filters and 575 fpm for washable type filters See Figure 16 The counterflow filter kit part number FR25 comes with two washable filters If not installing the FR25 kit remember not to exceed 400 fpm...

Page 30: ...electrical switch should be turned off prior to removing the access door Refer to Figure 18 below FIGURE 18 FILTER INSTALLATION LO BOY MODELS STEP 2 REMOVE BLOWER DOOR BY PULLING OUT ON SWELL LATCHES...

Page 31: ...this primary control A Flame Failure Simulate by shutting off oil supply manual valve while burner is on Within 9 seconds the control will shut the burner down and flash a diagnostic code of 1 2 seco...

Page 32: ...e burner tube and combustion chamber may be assured prior to installation into the furnace See Figure 19 and 20 WARNING The procedures described in Figures 19 and 20 should be conducted only by a qual...

Page 33: ...ght and left hand corners of the front plate Pull entire assembly straight back away from furnace BE CAREFUL NOT TO TIP ASSEMBLY UP OR DOWN AS IT MAY DAMAGE THE COMBUSTION CHAMBER See Figure 20 BURNER...

Page 34: ...ducts are detrimental to the life expectancy of the combustion chamber and will destroy the chamber Refer to the Cleaning of Furnace section for proper cleaning methods COMMON CAUSES OF TROUBLE CAUTIO...

Page 35: ...l B w o L 6 0 2 1 7 1 1 2 w o L m u i d e M 0 1 7 1 3 2 0 3 h g i H m u i d e M 4 1 1 2 1 3 8 3 h g i H 0 2 0 3 0 4 0 5 CHART 4 FLF FLR085D36E DATA d e e p S r e w o l B c i t a t S r e w o l B w o L...

Page 36: ...a t S r e w o l B w o L 5 0 4 1 7 1 4 2 w o L m u i d e M 8 0 7 1 2 2 0 3 h g i H m u i d e M 1 1 0 2 7 2 5 3 h g i H 0 2 0 3 0 4 0 5 CHART 8 FC085D36E DATA d e e p S r e w o l B c i t a t S r e w o l...

Page 37: ...PR3 3 4 240 210 180 150 R W G Y C BLOWER CONTROL T T L1 SEC2 SEC1 HEAT HUM 0 55 LOW RED 70 100 0 65 LOW RED 70 100 0 75 MED BLUE 60 90 0 85 LOW RED 70 100 1 MED LOW ORANGE 60 90 0 85 LOW RED 60 90 1 M...

Page 38: ...ACK 0 75 MED BLUE 60 90 HIGH BLACK 0 85 MED HIGH BLUE 60 90 HIGH BLACK 1 MED HIGH BLUE 60 90 HIGH BLACK 1 1 MED HIGH BLUE 60 90 HIGH BLACK 1 25 MED HIGH BLUE 60 90 HIGH BLACK FLR140D60E UNIT GPH INPUT...

Page 39: ...SCONNECT POWER BEFORE SERVICING DANGER DASHED LINES REPRESENT FIELD WIRING ONLY ONE HEATING AND COOLING SPEED CAN BE CONNECTED ALL OTHER TAPS CONNECT TO SPARE TERMINALS COOLING SPEED CONNECTION POINT...

Reviews: