background image

Manual 2100-422N
Page

20 of 42

1.

PREPARATION STEPS

A.

Calibrate and Check Operation of
Measuring Equipment  

 Follow

manufacturer’s recommended procedures for
calibration and equipment check out.

B.

Prepare Heating Unit for Testing  

 Drill two

1/4 inch holes in the flue between the heating
plant and the barometric draft regulator. If
space permits, the holes should be located in a
straight section of the flue, at least two flue
diameters from the elbow in the flue pipe and
at least one diameter from the draft regulator.
The purpose of the two holes in the flue pipe is
to speed up testing and reduce instrument
handling.

C.

Clean and Seal Heating Plant  

 Make sure the

burner blast tube, fan housing, and blower
wheel are clear of dirt and lint.  Seal any air
leaks into the combustion chamber.

D.

Nozzle Inspection

  Annual replacement of

nozzle is recommended.  The nozzle size
should match the design load.  DO NOT
OVERSIZE.  (Determination of oversizing can
be determined prior to your adjustment.  If the
firing rate should be reduced refer to Table 4.)
Short cycles and low percent “on” time result
in higher overall pollutant emissions and lower
thermal efficiency.  An in-line oil filter will
reduce service problems due to nozzle
clogging.

The filter should be located as close as possible
to the oil burner.  Care should be taken to
prevent air leakage in the oil suction line.  Use
continuous runs of copper tubing and use
minimum number of joints and fittings.
Always use flare fittings.

E.

Adjustment of Electrodes

   Adjust ignition

electrodes as specified in Figure 10.

F.

Operate Burner

    Operate burner, adjust air

setting for good flame by visual observation,
and run for at least 10 minutes or until
operation has stabilized.

G.

Check Burner Pressure

   Bleed air from

pump and nozzle piping.  Check pump
pressure and adjust to nameplate pump
pressure, if necessary.

2.

COMBUSTION ADJUSTMENT STEPS

H.

Set Draft

   Check the draft reading over the

fire with a draft gauge through a hole in the
inspection door.  The hole is above the flame
level.  Adjust the barometric draft regulator on
the flue to give the over fire of -.02" W.C.

I.

Check Smoke Readings

   After burner has

been operating 5 or 10 minutes, take a smoke

measurement in the flue, following the smoke
tester instructions.  Oily or yellow smoke spots
on the filter paper are usually a sign of
unburned fuel, indicating very poor combustion
(and likely high emissions of carbon monoxide
and unburned hydrocarbons).  This condition
can sometimes be caused by too much air, or by
other factors.  If this condition cannot be
corrected, major renovation or even burner
replacement may be necessary.

J.

Develop Smoke - CO2 Curve

   Record

measurements of smoke and CO

2

 from the flue.

Then establish the smoke - CO

2

 curve by taking

readings over a range of air settings, as shown
in Figure 8.

To do this, start with the air gate set at nearly
full open and then take smoke and CO

2

readings at progressively lower air settings, as
necessary to visualize the general shape of the
curve.  (The CO

2

 readings will increase as the

air setting is decreased, unless combustion is
incomplete.)  Do not set the air gate to give  a
smoke reading above No. 4 or No. 5.  Plot the
points on graph paper, as in Figure 8.  Usually
3 or 4 readings are enough to establish the
curve.

In adjusting each air setting, it is helpful to note
the various positions of air gate at which
measurements are made so that the final setting
can be located quickly.

K.

Adjust Air Setting

  Examine the smoke - CO

2

plot and, keeping in mind the curve of Figure 6,
note the location of the “knee” where the smoke
number begins to rise sharply.  Noting the air
gate position marks, adjust the air setting to a
CO

2

 level 1/2 to 1 percent lower than the CO

2

level at the “knee”.  (This provides a tolerance
against possible shifts in the setting over a
period of time.)  Do not increase the air setting
any more than necessary on the lower portion
of the curve below the “knee”.

The characteristic curve for some burners may
not yield a distinct “knee” in the curve.  In such
cases, the setting should be made near the
minimum smoke, (using judgement).

Lock the air adjustment and repeat draft,
CO

and smoke measurements to make sure

the setting has not shifted.

3.

COMBUSTION DIAGNOSIS

L.

Check Performance

   A well-matched and

well-tuned burner should be capable of
operation with smoke not greater than No. 2
and at a CO

2

 level not less than 10%.

If this cannot be reached, check the following:

Summary of Contents for FH085D36F

Page 1: ...rbon Monoxide is invisible orderless and toxic Bard Manufacturing recommends a carbon monoxide alarm in your home even if you do not own a gas appliance Locate the carbon monoxide alarm in the living...

Page 2: ...Chart 4 FLF FLR085D36F Data 38 Chart 5 FLF FLR110D48F Data 38 Chart 6 FLF FLR110D60F Data 38 Chart 7 FLR140D60F Data 39 Chart 8 FC085D36F Data 39 FIGURES Figure 1 FLF R Models Dimensions 5 Figure 2 FH...

Page 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Page 4: ...oil burner must have a generous supply of combustion air to operate properly The flow of combustion and ventilating air must not be obstructed from reaching the furnace See Combustion Air Requirement...

Page 5: ...3 2 3 2 3 2 3 2 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 t n o r F t n o r F r a...

Page 6: ...AND FH110 SPECIFICATION SHEET 19 1 4 16 RETURN OPENING CUT OUT OPTIONAL OIL ENTRANCE OIL ENTRANCE FRESH AIR KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE OPTIONAL LOW VOLTAGE ENTRANCE FLUE KNOCKOUT RETURN O...

Page 7: ...AGE ENTRANCE REAR FLUE KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE ENTRANCE FRESH AIR LOW VOLTAGE KNOCKOUT OIL ENTRANCE FLUE KNOCKOUT OPTIONAL OPTIONAL OIL ENTRANCE SUPPLY OPENING 19 1 8 18 1 8 BOTTOM VIE...

Page 8: ...ent CFM and external static pressure ratings to insure proper air delivery capabilities On replacement installations particularly if equipment is oversized the duct systems can easily be undersized Mo...

Page 9: ...n r u B m u m i n i M t i u c r i C y t i c a p m A e m i T x a M e s u F y a l e D R C A H r o r e k a e r B t i u c r i C P H A L F P H A L F F 6 3 D 5 8 0 H F 1 0 6 5 1 1 3 7 3 1 6 5 7 1 7 1 9 5 1...

Page 10: ...ow voltage thermostat entrance Shut off switch if not fused power line must include fuse or circuit breaker To power source To thermostat and optional A C unit Air Boot knockout optional Inspection do...

Page 11: ...flue models remove appropriate cabinet knockout Mounting screws located under flue box cover Flue Box Cover L i n e d C h i m n e y Thimble Clean out Door keep closed Oil Burner MIS 1825 Follow all a...

Page 12: ...must comply with NFPA31 BECKETT AFG OR NX OIL BURNER This furnace is equipped with a high static Beckett AFG or Beckett NX oil burner which is designed to produce adequate draft in nearly any vertical...

Page 13: ...troubleshooting features to ease service and reduce down time The operational guide for the Genisys 7505 primary control is provided following on Page 14 BECKETT SOLID STATE IGNITER This igniter diff...

Page 14: ...rryover Once flame is established the igniter remains on for 10 additional seconds to ensure flame stability 6 Run The flame is sustained until the call for heat is satisfied The burner is then sent t...

Page 15: ...b t e s e r e h t r e t f A e b n e h t n a c n o t t u b e h t s d n o c e s 5 1 e c n e u q e s n o i t i n g i t x e n e h t g n i r u d d e p p a t e d o m e m i r P p m u P r e t n e o t f f o t...

Page 16: ...ished during the four minute pump prime mode return to step 5 to re enter Pump Prime mode Repeat steps 5 through 7 until the pump is fully primed and the oil is free of bubbles 9 Terminate the call fo...

Page 17: ...gs This monitor system is available through your local distributor under the Honeywell Part QS7100F If the control locks out three times without a satisfied call for heat or due to other significant e...

Page 18: ...NECTIONS OIL PRIMARY T T CONNECTIONS LINE VOLTAGE CONNECTION HOT UNUSED BLOWER MOTOR SPEED CONNECTIONS LINE VOLTAGE CONNECTION COM L2 ELECTRIC AIR CLEANER CONNECTION HUMIDIFIER CONNECTION HEATING BLOW...

Page 19: ...H F G F A y o B i H 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 0 0 5 0 1 0 0 0 7 8 5 6 0 0 0 0 1 9 0 0 0 6 7 5 5 0 0 0 0 7 7 0 0 0 4 6 F 8 4 D 0 1 1 H F X N y o B i H 5 8 0 d i l o S 0 6 G I S P 0 5 1 0 0...

Page 20: ...Smoke Readings After burner has been operating 5 or 10 minutes take a smoke measurement in the flue following the smoke tester instructions Oily or yellow smoke spots on the filter paper are usually...

Page 21: ...icated if the net stack temperature during steady operation exceeds 600 F N Check Ignition Check operation over repeated cycles to insure prompt ignition on starting O Check Pump Cutoff Slow pump cuto...

Page 22: ...adjustment range 0 2 4 6 8 8 10 12 14 6 Knee Best air setting Plotted point Plotted point Plotted point CO Curve from plotted points 2 Air Settings Low High Bacharach Smoke Number Percent CO in Flue G...

Page 23: ...Manual 2100 422N Page 23 of 42 FIGURE 9 PRESSURE GAUGE CONNECTION TO BLEED PORT MIS 1660 Pressure Gauge Remove Bleed Port to attach pressure guage...

Page 24: ...RT UP SETTINGS l e d o M r e b m u N e l y t S r e n r u B o N t r a P e l z z o N d n a B r i A g n i t t e S r i A r e t t u h S g n i t t e S r i A t n e m t s u j d A e t a l P g n i t t e S e z i...

Page 25: ...te combustion of the fuel oil Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fuel oil When structures are constructed too tightly to supply s...

Page 26: ...THIS ASSEMBLE INNER FLANGE TO UNIT FOR AIR BOOT ACCORDING TO MANUAL IN LEFT SIDE REMOVE KNOCKOUT MAKE ALL SETTINGS REMOVE PUMP TO INTAKE AIR TUBE MIS 1833 AFG BURNER COMBUSTION AIR BOOT ASSEMBLY AFG...

Page 27: ...ppliances shall be provided For combustion air options see Page 25 Combustion Air Requirements NOTE Each opening shall have a free area of not less than one square inch per 1 000 BTU per hour 140 squa...

Page 28: ...per hour 70 square inches per gallon per hour of total input of all appliances in the enclosure FIGURE 13 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS NOTE Each air duct opening shall h...

Page 29: ...quare inches per gallon per hour of the total input rating of all appliances in the enclosure FIGURE 15 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPAC...

Page 30: ...of a corrosion resistant material having an upward pitch of 1 4 for every foot of horizontal run and be made of material capable of handling temperatures up to 1800 F A barometric damper is supplied w...

Page 31: ...0 0 2 m u i d e M 5 7 0 0 9 0 6 w o L F 6 3 D 5 8 0 F L F G F A 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 9 0 6 0 0 2 m u i d e M 5 6 0 0 9 0 6 w o L 5 5 0 0 9 0 6 w o L F 8 4 D 0 1 1 F L F X N 5 8 0 d i...

Page 32: ...e type filters and 575 fpm for washable type filters See Figure 16 The counterflow filter kit part number FR25 comes with two washable filters If not installing the FR25 kit remember not to exceed 400...

Page 33: ...cess door The electrical switch should be turned off prior to removing the access door Refer to Figure 18 below FIGURE 18 FILTER INSTALLATION LO BOY MODELS BY PULLING OUT ON SWELL LATCHES AND TILTING...

Page 34: ...in checking the safety switch in this primary control A Flame Failure Simulate by shutting off oil supply manual valve while burner is on Within 9 seconds the control will shut the burner down and fl...

Page 35: ...the burner tube and combustion chamber may be assured prior to installation into the furnace See Figure 19 and 20 WARNING The procedures described in Figures 19 and 20 should be conducted only by a q...

Page 36: ...and corners of the front plate Pull entire assembly straight back away from furnace BE CAREFUL NOT TO TIP ASSEMBLY UP OR DOWN AS IT MAY DAMAGE THE COMBUSTION CHAMBER See Figure 20 BURNER AND COMB CHAM...

Page 37: ...products are detrimental to the life expectancy of the combustion chamber and will destroy the chamber Refer to the Cleaning of Furnace section for proper cleaning methods COMMON CAUSES OF TROUBLE CA...

Page 38: ...e w o l B w o L 6 0 2 1 7 1 1 2 w o L m u i d e M 0 1 7 1 3 2 0 3 h g i H m u i d e M 4 1 1 2 1 3 8 3 h g i H 0 2 0 3 0 4 0 5 CHART 4 FLF FLR085D36FDATA d e e p S r e w o l B c i t a t S r e w o l B w...

Page 39: ...t a t S r e w o l B w o L 5 0 4 1 7 1 4 2 w o L m u i d e M 8 0 7 1 2 2 0 3 h g i H m u i d e M 1 1 0 2 7 2 5 3 h g i H 0 2 0 3 0 4 0 5 CHART 8 FC085D36F DATA d e e p S r e w o l B c i t a t S r e w...

Page 40: ...MIT PLUG 2 CAPACITOR BLACK WHITE RETURN AREA BLOWER PRIMARY CONN 24V UNIT Y C W Rh Y G Rc THERMOSTAT COND OR EQUIVELANT T87F Q539A1220 VOLTAGE LOW VOLTAGE HIGH 5 WIRING FIELD 5 3 LIMIT BLACK HEATING A...

Page 41: ...RS T87F Q539A1220 C BACKUP LIMIT CONTROL PANEL PRIMARY LIMIT 3 BLACK COOL SPR3 EAC COM SPR1 BLACK 1 4 BLUE BLUE YELLOW PURPLE PURPLE ORANGE GREEN GROUND BROWN BROWN T SEC1 HEAT RED 240 210 180 150 R W...

Page 42: ...TOR OIL VALVE BURNER ASS Y T T 1 24V CONN YELLOW HUM UNIT Y C W Rh Y BURNER T87F Q539A1220 CONTROL PANEL OR EQUIVELANT BLACK BLACK BLACK BLACK BLACK G HEAT EX AREA HOT 2 HEAT COND 2 PRIMARY LIMIT BACK...

Reviews: