background image

Manual 2100-422N
Page

8 of 42

 IMPORTANT

When a furnace is installed so that supply
ducts carry air circulated by the furnace to
areas outside the space containing the
furnace, the return air must also be handled
by a duct(s) sealed to the furnace casing and
terminating outside the space containing the
furnace  This is to prevent drawing possible
hazardous combustion products into the
circulated air.

INSTALLING THE FURNACE

INSTRUMENTS REQUIRED FOR PROPER
SETUP OF THE FURNACE

It is important that a set of instruments capable of the
following requirements be used for the setup of this
furnace to ensure proper and safe operation:

1. Oil pump pressure gauge that measures up to

150 PSI.

2. Smoke gun to pull smoke samples from flue.

3. Draft gauge that will measure -.02" water column

(W.C.)

4. Duct static pressure gauge 0-1.0" W.C. range.

5. Temperature gauge that can read from 50° F up to

700° F.

6. A gauge to measure CO

2

 or O

2

.

INSTALLATION

A typical installation is shown in Figures 4 and 5.  All
parts of the furnace installation (furnace, oil tank and
piping systems, combustion and ventilation air, venting,
etc.) must comply with NFPA31, Installation of Oil
Burning Equipment -- latest edition.  This drawing
shows the typical connecting parts needed to correctly
install this furnace.  Make sure that all parts of the
heating system comply with the local codes.

Check the furnace and your load calculation to verify
that the unit is properly sized.  (Refer to “Equipment
Selection” section on Page 4.)

The correct size of unit needed may be substantially
smaller than the unit being replaced due to home
improvements and technology advancements since the
initial installation.

INADEQUATE SUPPLY AIR and/or RETURN
AIR DUCT SYSTEMS

Short cycling because of limit control operation can be
created by incorrectly designed or installed supply and/
or return air duct systems.

The duct systems must be designed using ASHRAE or
ACCA design manuals and the equipment CFM and
external static pressure ratings to insure proper air
delivery capabilities.

On replacement installations, particularly if equipment
is oversized, the duct systems can easily be undersized.
Modifications may be required to assure that the
equipment is 

operating within the approved

temperature rise range when under full rated input
conditions

, and that no short cycling on limit controls is

occurring.

DUCT WORK

The air distribution system should be designed and
installed in conformance with manuals published by
Air Conditioning Contractors of America (ACCA) as
set forth in Manual D, or ASHRAE publications.

INSTALLING A COOLING UNIT

When the furnace is used in connection with a cooling
unit

*

, the furnace shall be installed parallel with or on

the upstream side of the cooling unit to avoid
condensation in the heating element.  With a parallel
flow arrangement, the dampers or other means used to
control flow of air shall be adequate to prevent chilled
air from entering the furnace, and if manually operated,
must be equipped with means to prevent operation of
either unit, unless the damper is in the full heat or cool
position.

*

A cooling unit is an air conditioning coil, heat
pump coil or chilled water coil.

When installing a cooling unit above an FH or FL
(below on an FC) series furnace, the coil must be
spaced far enough from the furnace outlet to assure
proper operation of the furnace.  Bard supplied coils,
when used with Bard supplied coil cabinets, are
automatically positioned.

For top discharge FH and FL models, when coils are
installed without using Bard coil cabinets or coils of
another brand are used, the coil drain pan should be
located a minimum of four (4) inches above the top of
the furnace cabinet.  If a greater clearance is specified
by the coil manufacturer then it would apply.

NOTE: IF DRAIN PAN IS ANYTHING OTHER

THAN A STEEL PAN PARTICULAR
ATTENTION MUST BE GIVEN TO THE
INSTALLATION INSTRUCTIONS FOR
THE COIL TO MAKE SURE IT IS
ACCEPTABLE FOR USE WITH THESE
OIL FURNACES HAVING MAXIMUM
OUTLET AIR TEMPERATURE OF 200° F.

See CFM versus static pressure curves on pages 38-39
for additional information.

Summary of Contents for FH085D36F

Page 1: ...rbon Monoxide is invisible orderless and toxic Bard Manufacturing recommends a carbon monoxide alarm in your home even if you do not own a gas appliance Locate the carbon monoxide alarm in the living...

Page 2: ...Chart 4 FLF FLR085D36F Data 38 Chart 5 FLF FLR110D48F Data 38 Chart 6 FLF FLR110D60F Data 38 Chart 7 FLR140D60F Data 39 Chart 8 FC085D36F Data 39 FIGURES Figure 1 FLF R Models Dimensions 5 Figure 2 FH...

Page 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Page 4: ...oil burner must have a generous supply of combustion air to operate properly The flow of combustion and ventilating air must not be obstructed from reaching the furnace See Combustion Air Requirement...

Page 5: ...3 2 3 2 3 2 3 2 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 t n o r F t n o r F r a...

Page 6: ...AND FH110 SPECIFICATION SHEET 19 1 4 16 RETURN OPENING CUT OUT OPTIONAL OIL ENTRANCE OIL ENTRANCE FRESH AIR KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE OPTIONAL LOW VOLTAGE ENTRANCE FLUE KNOCKOUT RETURN O...

Page 7: ...AGE ENTRANCE REAR FLUE KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE ENTRANCE FRESH AIR LOW VOLTAGE KNOCKOUT OIL ENTRANCE FLUE KNOCKOUT OPTIONAL OPTIONAL OIL ENTRANCE SUPPLY OPENING 19 1 8 18 1 8 BOTTOM VIE...

Page 8: ...ent CFM and external static pressure ratings to insure proper air delivery capabilities On replacement installations particularly if equipment is oversized the duct systems can easily be undersized Mo...

Page 9: ...n r u B m u m i n i M t i u c r i C y t i c a p m A e m i T x a M e s u F y a l e D R C A H r o r e k a e r B t i u c r i C P H A L F P H A L F F 6 3 D 5 8 0 H F 1 0 6 5 1 1 3 7 3 1 6 5 7 1 7 1 9 5 1...

Page 10: ...ow voltage thermostat entrance Shut off switch if not fused power line must include fuse or circuit breaker To power source To thermostat and optional A C unit Air Boot knockout optional Inspection do...

Page 11: ...flue models remove appropriate cabinet knockout Mounting screws located under flue box cover Flue Box Cover L i n e d C h i m n e y Thimble Clean out Door keep closed Oil Burner MIS 1825 Follow all a...

Page 12: ...must comply with NFPA31 BECKETT AFG OR NX OIL BURNER This furnace is equipped with a high static Beckett AFG or Beckett NX oil burner which is designed to produce adequate draft in nearly any vertical...

Page 13: ...troubleshooting features to ease service and reduce down time The operational guide for the Genisys 7505 primary control is provided following on Page 14 BECKETT SOLID STATE IGNITER This igniter diff...

Page 14: ...rryover Once flame is established the igniter remains on for 10 additional seconds to ensure flame stability 6 Run The flame is sustained until the call for heat is satisfied The burner is then sent t...

Page 15: ...b t e s e r e h t r e t f A e b n e h t n a c n o t t u b e h t s d n o c e s 5 1 e c n e u q e s n o i t i n g i t x e n e h t g n i r u d d e p p a t e d o m e m i r P p m u P r e t n e o t f f o t...

Page 16: ...ished during the four minute pump prime mode return to step 5 to re enter Pump Prime mode Repeat steps 5 through 7 until the pump is fully primed and the oil is free of bubbles 9 Terminate the call fo...

Page 17: ...gs This monitor system is available through your local distributor under the Honeywell Part QS7100F If the control locks out three times without a satisfied call for heat or due to other significant e...

Page 18: ...NECTIONS OIL PRIMARY T T CONNECTIONS LINE VOLTAGE CONNECTION HOT UNUSED BLOWER MOTOR SPEED CONNECTIONS LINE VOLTAGE CONNECTION COM L2 ELECTRIC AIR CLEANER CONNECTION HUMIDIFIER CONNECTION HEATING BLOW...

Page 19: ...H F G F A y o B i H 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 0 0 5 0 1 0 0 0 7 8 5 6 0 0 0 0 1 9 0 0 0 6 7 5 5 0 0 0 0 7 7 0 0 0 4 6 F 8 4 D 0 1 1 H F X N y o B i H 5 8 0 d i l o S 0 6 G I S P 0 5 1 0 0...

Page 20: ...Smoke Readings After burner has been operating 5 or 10 minutes take a smoke measurement in the flue following the smoke tester instructions Oily or yellow smoke spots on the filter paper are usually...

Page 21: ...icated if the net stack temperature during steady operation exceeds 600 F N Check Ignition Check operation over repeated cycles to insure prompt ignition on starting O Check Pump Cutoff Slow pump cuto...

Page 22: ...adjustment range 0 2 4 6 8 8 10 12 14 6 Knee Best air setting Plotted point Plotted point Plotted point CO Curve from plotted points 2 Air Settings Low High Bacharach Smoke Number Percent CO in Flue G...

Page 23: ...Manual 2100 422N Page 23 of 42 FIGURE 9 PRESSURE GAUGE CONNECTION TO BLEED PORT MIS 1660 Pressure Gauge Remove Bleed Port to attach pressure guage...

Page 24: ...RT UP SETTINGS l e d o M r e b m u N e l y t S r e n r u B o N t r a P e l z z o N d n a B r i A g n i t t e S r i A r e t t u h S g n i t t e S r i A t n e m t s u j d A e t a l P g n i t t e S e z i...

Page 25: ...te combustion of the fuel oil Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fuel oil When structures are constructed too tightly to supply s...

Page 26: ...THIS ASSEMBLE INNER FLANGE TO UNIT FOR AIR BOOT ACCORDING TO MANUAL IN LEFT SIDE REMOVE KNOCKOUT MAKE ALL SETTINGS REMOVE PUMP TO INTAKE AIR TUBE MIS 1833 AFG BURNER COMBUSTION AIR BOOT ASSEMBLY AFG...

Page 27: ...ppliances shall be provided For combustion air options see Page 25 Combustion Air Requirements NOTE Each opening shall have a free area of not less than one square inch per 1 000 BTU per hour 140 squa...

Page 28: ...per hour 70 square inches per gallon per hour of total input of all appliances in the enclosure FIGURE 13 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS NOTE Each air duct opening shall h...

Page 29: ...quare inches per gallon per hour of the total input rating of all appliances in the enclosure FIGURE 15 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPAC...

Page 30: ...of a corrosion resistant material having an upward pitch of 1 4 for every foot of horizontal run and be made of material capable of handling temperatures up to 1800 F A barometric damper is supplied w...

Page 31: ...0 0 2 m u i d e M 5 7 0 0 9 0 6 w o L F 6 3 D 5 8 0 F L F G F A 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 9 0 6 0 0 2 m u i d e M 5 6 0 0 9 0 6 w o L 5 5 0 0 9 0 6 w o L F 8 4 D 0 1 1 F L F X N 5 8 0 d i...

Page 32: ...e type filters and 575 fpm for washable type filters See Figure 16 The counterflow filter kit part number FR25 comes with two washable filters If not installing the FR25 kit remember not to exceed 400...

Page 33: ...cess door The electrical switch should be turned off prior to removing the access door Refer to Figure 18 below FIGURE 18 FILTER INSTALLATION LO BOY MODELS BY PULLING OUT ON SWELL LATCHES AND TILTING...

Page 34: ...in checking the safety switch in this primary control A Flame Failure Simulate by shutting off oil supply manual valve while burner is on Within 9 seconds the control will shut the burner down and fl...

Page 35: ...the burner tube and combustion chamber may be assured prior to installation into the furnace See Figure 19 and 20 WARNING The procedures described in Figures 19 and 20 should be conducted only by a q...

Page 36: ...and corners of the front plate Pull entire assembly straight back away from furnace BE CAREFUL NOT TO TIP ASSEMBLY UP OR DOWN AS IT MAY DAMAGE THE COMBUSTION CHAMBER See Figure 20 BURNER AND COMB CHAM...

Page 37: ...products are detrimental to the life expectancy of the combustion chamber and will destroy the chamber Refer to the Cleaning of Furnace section for proper cleaning methods COMMON CAUSES OF TROUBLE CA...

Page 38: ...e w o l B w o L 6 0 2 1 7 1 1 2 w o L m u i d e M 0 1 7 1 3 2 0 3 h g i H m u i d e M 4 1 1 2 1 3 8 3 h g i H 0 2 0 3 0 4 0 5 CHART 4 FLF FLR085D36FDATA d e e p S r e w o l B c i t a t S r e w o l B w...

Page 39: ...t a t S r e w o l B w o L 5 0 4 1 7 1 4 2 w o L m u i d e M 8 0 7 1 2 2 0 3 h g i H m u i d e M 1 1 0 2 7 2 5 3 h g i H 0 2 0 3 0 4 0 5 CHART 8 FC085D36F DATA d e e p S r e w o l B c i t a t S r e w...

Page 40: ...MIT PLUG 2 CAPACITOR BLACK WHITE RETURN AREA BLOWER PRIMARY CONN 24V UNIT Y C W Rh Y G Rc THERMOSTAT COND OR EQUIVELANT T87F Q539A1220 VOLTAGE LOW VOLTAGE HIGH 5 WIRING FIELD 5 3 LIMIT BLACK HEATING A...

Page 41: ...RS T87F Q539A1220 C BACKUP LIMIT CONTROL PANEL PRIMARY LIMIT 3 BLACK COOL SPR3 EAC COM SPR1 BLACK 1 4 BLUE BLUE YELLOW PURPLE PURPLE ORANGE GREEN GROUND BROWN BROWN T SEC1 HEAT RED 240 210 180 150 R W...

Page 42: ...TOR OIL VALVE BURNER ASS Y T T 1 24V CONN YELLOW HUM UNIT Y C W Rh Y BURNER T87F Q539A1220 CONTROL PANEL OR EQUIVELANT BLACK BLACK BLACK BLACK BLACK G HEAT EX AREA HOT 2 HEAT COND 2 PRIMARY LIMIT BACK...

Reviews: