Manual 2100-579A
Page
27 of 41
TABLE 5 — CORRELATION OF PERCENT OF CO
2
, O
2
AND RESERVE AIR
TABLE 6 — NO. 2 FUEL OIL EFFICIENCY CHART (NET STACK TEMP. DEGREES F)
TABLE 7 — RECOMMENDED START-UP SETTINGS
Carbon Dioxide
Oxygen
Reserve Air (Approx.)
15.4
15.0
14.5
0.0
0.6
1.2
0.0
3.0
6.0
14.0
13.5
13.0
2.0
2.6
3.3
10.0
15.0
20.0
12.5
12.0
11.5
4.0
4.6
5.3
25.0
30.0
35.0
11.0
10.5
10.0
6.0
6.7
7.4
40.0
45.0
50.0
% O
2
200
250
300
350
400
450
500
550
600
650
700
750
800
% O
2
1
89.6
88.4
87.3
86.2
85.1
84.0
82.9
81.7
80.6
79.5
78.4
77.3
76.2
14.7
2
89.4
88.2
87.0
85.9
84.7
83.6
82.4
81.2
80.1
78.9
77.7
76.6
75.4
14.0
3
89.2
87.9
86.7
85.5
84.3
83.1
81.9
80.7
79.4
78.2
77.0
75.8
74.6
13.2
4
88.9
87.7
86.4
85.1
83.8
82.6
81.3
80.0
78.7
77.5
76.2
74.9
73.6
12.5
5
88.7
87.3
86.0
84.6
83.3
82.0
80.6
79.3
77.9
76.6
75.3
73.9
72.6
11.7
6
88.4
87.0
85.5
84.1
82.7
81.3
79.9
78.5
77.0
75.6
74.2
72.8
71.4
11.0
7
88.0
86.5
85.0
83.5
82.0
80.5
79.0
77.5
76.0
74.5
73.0
71.5
70.0
10.3
Model
Number
Burner
Type
Nozzle
Air Adjustment
Plate Setting
Size
Type
Pump
Pressure
FLR075V42A
NX
0.50
60 DEG. SOLID
175 PSIG
2.50
FLF075V42A
NX
0.50
60 DEG. SOLID
175 PSIG
2.50
FLR100V48A
NX
0.75
60 DEG. SOLID
150 PSIG
3.25
FLR100V60A
NX
0.75
60 DEG. SOLID
150 PSIG
3.25
FLR130V60A
NX
0.85
60 DEG. SOLID
175 PSIG
3.25