Manual 2100-578L
Page
17 of 42
(2) Unit
Drain Entrances
Drain Area
Drains
Insulate
(2) Optional Unit
(2) Drain
Access
Locations
MIS-3115 A
(2) OPTIONAL DRAIN
HOLES IN BASE
WALL
BASE VIEW
16 1/2"
18 3/4"
7 3/16"
40 3/4"
35"
OPTIONAL FLOOR
MOUNTING HOLES
CONDENSATE DRAIN
There are two condensate drain connections from the
condenser drain pan (compressor area). These are
visible from the rear of the unit. Factory-installed
tubing connects the two drains at a tee connection and
then a single drain hose with a barbed hose connector
carries the condensate to the draining option chosen.
Enough tubing is provided to reach all drain options
and can be cut down in length.
The unit is shipped from the factory with the drain
line on the left-hand side when looking at the rear of
the unit. The tubing can be removed from the drain
connections and flipped for a right-hand drain. See
Figure 8.
The drain can be routed directly through the floor or
through the wall. There are also two optional drain
locations in the lower rear back panel. See Figure 8.
The I-TEC design does not require a trap in the
condensate disposal tubing. Check local codes to see
if a “P” trap is required.
For a stand pipe floor drain or through the wall, there
is adequate hose length to reach needed location
behind the unit. The lower rear portion of the cabinet is
recessed approximately 4" allowing room for a “P” trap
(if required) to be installed with the cabinet flush with
the wall. Keep in mind, the drain line must be able to
be removed from the unit if necessary to remove the unit
from the wall.
Access plates are located on the rear of the unit for
servicing the drain trap. See Figure 8.
If the drain line
is to be routed through an unconditioned space, it must
be protected from freezing.
The condensate drain line can also be routed back
into the unit through either the right-hand or left-hand
optional drain locations on the rear of the unit. The hole
is covered by insulation on the inside of the unit and
will have to be cut away. Located inside the unit, about
12" in from the front on both the left and right side are
drain holes in the bottom of the base. These holes are
covered with insulation and are not visible from inside
vent option area. They are located very close to the
side panels and can be found by pressing down on the
insulation or looking at back of vent option area (See
Figure 8). Cut insulation away to expose the hole. A
drain trap can now be installed inside of the cabinet,
and the drain hose routed directly through the floor.
Once the I-TEC is installed, the rear drains exiting the
condenser section can be easily serviced with removal
of the pre-painted metal sides (lift-off doors, remove
four [4] screws to remove side).
If side access is not available, the drain lines and trap
can be serviced by removing either one of the drain
access panels on the rear of the unit (in the ventialtion
package area.) See Figure 8.
A
fter drain installation is complete, drain area must
be insulated for sound purposes with 45" x 24¾" x 6"
piece of insulation. See Figure 8.
With No Vent Option
To remove the drain access panels in the rear of this
section, simply remove the front door/cover from the
box. Rear drain access panels are now visible on both
right-hand and left-hand sides in rear of box.
With Commercial Room Ventilator
1. Open hinged front doors.
2. Disconnect unit power to eliminate shock hazard.
3. Remove front cover/door of CRV vent package. (Can
leave filter access panels in place.)
4. Unplug wires coming in on left side from upper
unit section.
5. Unplug two wire harness from front (intake) blower.
6. Remove two (2) screws securing front (intake)
blower and slide blower out of unit.
7. Remove four (4) screws that retian the partition
behind/beneath intake blower removed in Step #6.
8. Rear drain access panels are now visible on both
right-hand and left-hand sides in rear of box.
FIGURE 8
Drain Locations