background image

Manual 2100-597G
Page 

46 of 68

FIGURE 27 

Control Board Configuration/Setting

CONFIGURING BARD PART #8403-067 

CO

2

 CONTROL for CRV MODULATING 

CONTROL 

Bard part #8403-067

 C

arbon dioxide and temperature 

transmitters accurately monitor the CO

2

 concentration 

and temperature in schools, office buildings and 
other indoor environments to help achieve LEED® 
certification.

Specifications

Range:

 CO

2

: 0 to 2000 or 0 to 5000 ppm (depending 

on model)

 

Temperature: 32 to 122°F (0 to 50°C)

Accuracy:

 ±40 ppm + 3% of reading

Temperature Dependence:

 

±8 ppm/°C at 1100 ppm

Non-Linearity:

 16 ppm

Pressure Dependence:

 0.13% of reading per mm of Hg

Response Time:

 2 minutes for 99% step change

Ambient Operating Temperature:

 32 to 122°F (0 to 50°C)

Ambient Operating Humidity:

 10 to 95% RH  

(non-condensing)

Power Requirements:

 16 to 35 VDC/19 to 28 VAC

Power Consumption:

 Average: 2 watts;  

Peak: 3.75 watts

Move jumper pin to “P” 
position to allow variable 
ventilation control using 0-10 
VDC CO

2

 controller

Board mode pins factory 
shipped on “M” pin for On/Off 
control scheme using “A” signal 
on low voltage control board

“Red” status light (on 
when unit has power)

“Green” signal light continuously 
indicates the flow index the 
blower is producing.  After a 
pause, the lamp will flash out 
long digits which will indicate 
the “TENS” count, which is 
immediately followed by short 
flashes between 1 and 99.  For 
example, a flow index of 23 would 
yield two long flashes and three 
short flashes.

Manual adjust screw.  Use when operating in manual mode (“M” 
jumper installed) along with the “GREEN SIGNAL LIGHT” to 
adjust to the required CFM of ventilation.  CW rotation reduces the 
“FLOW INDEX”, CCW rotation increases the “FLOW INDEX”.

Series 1

EVO™/ECM-ACU+

Evolution Controls Inc.

p.3 of 4.

©Evolution Controls Inc.

12

-May

-09

0.265"

ø

0.1

87

5"

Us

e #

8 F

lath

ea

d

Use 
4mm 

Flathead

1.133"

1.429"

36.30mm

1.793"

45.54mm

64.01mm

2.520"

28.78mm

6.73mm

21

.3

9m

m

0.

84

2"

44

.4

5m

m

1.

75

0"

RPM Out

Neutral/Common

24Vac/dc

24Vac/dc

Common

Signal Common

Control Signal

Class II Power Source

Earth neutral/Common

at transformer

for electrical safety.

Signal Common,

Aux Common &

Neutral/Common are

internally connected

Aux

Power

ECM Motor Control Cable

To Automation

Controller

0-2,000 RPM

= 0-10Vdc

Mounting

Mount the ACU+ inside a metal control cabinet or 

enclosure.  Fasten the mounting posts to an earthed metal 

surface.

Mount the ACU+ with clearance for the 24Vac power wires,

automation wires and control cable connector.  Mount the 

control so the signal lamps are visible. Make Adjust

accessible if it is used in your application. The control may 

be surface mounted, or reverse mounted so the LEDs and 

control shaft are visible through the enclosure wall. For

surface mount, a silver or white surface under the LEDs 

makes them more visible from the component side of the 

ACU+. The control’s motor cable connector is small so it 

may be carefully pulled through an empty 3/4” conduit. 

Keep high voltage wiring away from the ACU+ circuitry or 

wiring.  Follow electrical code requirements for separation of 

high and low voltage wiring and components.

Wiring

Power the EVO/ECM-ACU+ with a 24Vac NEC Class II 

USA

power limited transformer

3

. Observe all code requirements 

and follow all safety practices regarding low voltage power supplies and circuits to insure a safe, reliable installation.

Some applications may require an isolated power supply or alternative earthing scheme.  Follow code requirements and

carefully observe all safety practices concerning unearthed low voltage circuits. 

Earth one lead of the 24 Vac side of the power transformer

4

.  Connect the ACU+ neutral connection to the earthed lead.

Connect the 24Vac 50/60Hz connection to the hot side of the 24 Vac Class II power source. With the “P” jumper out,

you may interrupt this connection as a means to stop the ECM Motor.    Most automation controllers will power the 

ACU+ directly from a 24 Vac on/off output, eliminating the fan relay. Automation controllers that switch neutral may 

require a fan relay.

The signal input is single-ended, so power neutral and signal common are internally connected.

Connect the 0-10 Vdc control signal 

to the Signal connection.  Connect 

the control signal common to the 

Neutral connection.

The input presents a 21K ohm load 

to the signal source.  Include this 

resistance when calculating a 

dropping resistor for 4-20 Ma 

operation. A 511 ohm 1% resistor

5

provides a 500 ohm dropping 

resistance.

Connect to the motor using an 

EVO/ECM-CBL motor control cable.

3

See NEC

USA

725.41

4

NEC

USA

250.20.a.

5

www.Mouser.com

pn. 271-511-RC

Series CDT Carbon Dioxide and Temperature Transmitters

accurately monitor

the  CO2 concentration  and  temperature  in  schools,  office  buildings,  and  other

indoor  environments  to  help  achieve  LEED®  certification.  For  increased  sensor

life, a single- beam dual-wavelength non-dispersive infrared (NDIR) sensor is used

to  automatically  correct  the  measurement  in  both  occupied  and  unoccupied

buildings  against  aging  effects.  The  single-beam  dual-wavelength  sensor

technology provides the highest level of accuracy compared to Automatic Baseline

Correction methods which can unintentionally shift the calibration based on CO

2

levels  and  barometric  pressure  conditions.  In  order  to  achieve  a  higher  level  of

accuracy, the Series CDT includes digital barometric pressure adjustment and the

ability to field-calibrate the sensor.

Universal outputs allow users to select the transmitter output to be 4 to 20 mA, 0

to 5 VDC or 0 to 10 VDC to work with virtually any building management controller.

An optional relay with user adjustable set points can be used to control exhaust

fans, open actuated windows or dampers, or signal a light or horn.

For applications that require visual indication, the Series CDT can be ordered with

an integral LCD display or the Model A-449 remote LCD display that can plug into

the  mini-connector  port  on  the  side  of  the  transmitter.  The  display  can  be

configured to display temperature only, CO

2

 only or CO

2

and temperature together.

Push buttons are standard on the transmitters for access to the menu structure,

but the transmitter can be ordered without the buttons. To prevent tampering, the

action of the buttons can be locked out using an internal jumper selection. Menu

items  that  can  be  accessed  include:  engineering  units,  relay  output  set  points,

display configuration, transmitter output scaling, ambient barometric pressure and

field calibration of the transmitter.

Single beam dual-wavelength sensor advantages:

• Automatically corrects for aging effects in occupied and unoccupied buildings

o

Perfect for hospitals and manufacturing plants that are occupied 24 hours per 

day

• Measures actual unfiltered light intensity directly

o

Eliminates error from incorrect assumptions of gas concentration in theoretical 

logic assumption methods

Series CDT Carbon Dioxide/Temperature Transmitter

Specifications - Installation and Operating Instructions

Bulletin AQ-CDT

DWYER INSTRUMENTS, INC. 

phone: 219/879-8000

www.dwyer-inst.com

p.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. 

fax: 219/872-9057

e-mail: info@dwyer-inst.com

SpECIfICATIONS

Range: 

CO

2

: 0 to 2000 or 0 to 5000 ppm (depending on model);

Temperature: 32 to 122°F (0 to 50°C).

Accuracy: 

±40 ppm + 3% of reading.

Temperature Dependence:

±8 ppm / °C at 1100 ppm.

Non-Linearity: 

16 ppm.

pressure Dependence: 

0.13% of reading per mm of Hg.

Response Time: 

2 minutes for 99% step change.

Ambient Operating Temperature: 

32 to 122°F (0 to 50°C).

Ambient Operating Humidity: 

10 to 95% RH (non-condensing).

power Requirements: 

16 to 35 VDC / 19 to 28 VAC.

power Consumption: 

Average: 2 watts; Peak: 3.75 watts.

Sensor: 

Single beam, dual-wavelength NDIR.

Output: 

Current: 4 to 20 mA (max 500 Ω);

Voltage: 0 to 5 VDC or 0 to 10 VDC (min 500 Ω);

Relay: SPST NO 2A @ 30 VDC;

RTD or thermistor per r-t curves (depending on model).

Weight:

5.6 oz (158.8 g).

4-31/64

[113.9]

3-13/32

[86.52]

35/64

[13.89]

1-13/32

[35.72]

1-53/64

[46.43]

3x 3/8

[9.53]

1-13/32

[50.01]

1-3/16

[30.20]

1-3/16

[30.20]

7/8

[22.35]

4x 3/16

[4.76]

INSTALLATION

Disconnect power supply before installation to prevent electrical

shock and equipment damage.

Make sure all connections are in accordance with the job wiring diagram and in

accordance with national and local electrical codes. Use copper conductors only.

Use electrostatic discharge precautions (e.g., use of wrist straps)

during installation and wiring to prevent equipment damage.

Avoid  locations  where  severe  shock  or  vibration,  excessive

moisture or corrosive fumes are present.

Do  not  exceed  ratings  of  this  device,  permanent  damage  not

covered by warranty may result.

Upon powering the transmitter, the firmware version will flash on

the display. A warm up period of 30 minutes is required for the

                             

transmitter to adjust to the current CO

2

concentration.

Self  calibration  feature  of  the  transmitter  requires  exposure  to

normal outdoor equivalent carbon dioxide level once every thirty 

days.

WARNING

CAUTION

CAUTION

CAUTION

NOTICE

NOTICE

Sensor:

 Single beam, dual-wave length NDIR

Output:

 Current: 4 to 20 mA (max 500 Ω)

 

Voltage: 0 to 5 VDC or 0 to 10 VDC  
(min 500 Ω)

 

Relay: SPST NO 2A @ 30 VDC

 

RTD or thermistor per r-t curves  
(depending on model)

Weight:

 5.6 oz (158.8 g)

Summary of Contents for I30A1DA

Page 1: ...els INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 597G Supersedes 2100 597F Date 5 18 16 I30A1DA I30A1DB I30A1DC I36A1DA I36A1DB I36A1DC I42A1D...

Page 2: ...l Description 35 Control Wiring 35 Recommended Control Sequences 35 Setting the Ventilation CFM Levels 35 I TEC Combination CRV and Economizer Ventilation System Vent Code N 38 General Description 38...

Page 3: ...e 23 Motor Speed CFM Configuration 39 Figure 24A CRV Manual Mode M Terminal 43 Figure 24B CRV Mod Mode P Terminal 43 Figure 25 Ventilation Airflow Diagram 44 Figure 26 CRV Access 45 Figure 27 Control...

Page 4: ...l N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Conditioning Contr...

Page 5: ...ation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than...

Page 6: ...All units have 24V terminal block Motor will deliver consistent CFM through voltage supply range with no deterioration Continuous fan CFM is the total air being circulated during continuous fan mode W...

Page 7: ...C09 460 3 1 1 1 9 13 18 10 15 20 14 14 12 14 14 12 I36A1DA0Z A05 A10 A15 230 208 1 1 1 1 1 or 2 26 32 58 84 40 40 60 90 8 8 6 4 10 10 10 8 26 52 40 60 8 6 10 10 I36A1DB0Z B06 B09 B15 230 208 3 1 1 1 1...

Page 8: ...1 5 47 3 46 1 8 With Sides Removed Vent Intake Disconnect Electrical Air Filters Vent Exhaust Door Latch Locking Filters Return Air 2 12 x 20 Door Latch Locking Air Filters 2 Washable Hinges 4 Lift Of...

Page 9: ...oad is required to lift the top section off from the bottom base Do not attempt to do this manually Failure to do so could result in the unit tipping over and causing bodily injury and or damage to th...

Page 10: ...is required two riser platform accessories are available The IRP3 increases the unit height by 3 Figure 7B on page 15 and the IRP6 by 6 Figure 7C on page 16 SECURING UNIT TO STRUCTURE Shipped with th...

Page 11: ...s Optional Top Centered on Higher Sill Heights Acheivable With Base Kit Wall Opening Sleeve Mounting Hole Locations FLOOR MOUNTING HOLE CENTERLINES 17 8 56 8 20 6 7 20 2 8 8 29 32 7 1 20 7 8 43 7 42 3...

Page 12: ...Y Dimension Z Dimension Z Dimension I30A1DA DB 13 3 4 24 43 47 I30A1DC 13 3 4 24 43 47 I36A1DA DB 13 3 4 24 43 47 I36A1DC 13 3 4 24 43 47 I42A1DA DB 13 3 4 24 43 47 I42A1DC 13 3 4 24 43 47 I48A1DA DB...

Page 13: ...E WING WALL CONSTRUCTION TOP VIEW CLOSET CONSTRUCTION TOP VIEW LEFT CORNER CONSTRUCTION TOP VIEW FILTERS RIGHT CORNER CONSTRUCTION TOP VIEW ACCESS DIMENSIONS REMOVABLE SIDES 1 1 ALL FILTER AND COMPONE...

Page 14: ...Manual 2100 597G Page 14 of 68 FIGURE 6 Compressor Shipping Bolts COMPRESSOR SHIPPING BOLT COMPRESSOR SHIPPING BOLT FIGURE 5 Removal of Air Duct CRV ERV AIR DUCT...

Page 15: ...NDED TO BOTTOM OF ROOF 9 7 MINIMUM OR FIXED CEILING FLOOR OR FIXED CEILING BOTTOM OF ROOF SUSPENDED CEILING 20 MINIMUM 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED MINIMUM 12 4 MI...

Page 16: ...ENDED TO BOTTOM OF ROOF 9 10 MINIMUM OR FIXED CEILING 3 RISER FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED 12 MINIMUM 4 MINIMUM FROM TOP OF UNIT TO DUCT BOTTOM MIS 2989 B FLOOR OR FIXED CEILING BOTTO...

Page 17: ...IXED CEILING 6 RISER 9 8 MINIMUM REQUIRED INSTALLATION HEIGHT BOTTOM OF ROOF FLOOR OR FIXED CEILING SUSPENDED CEILING MINIMUM 20 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT MIS 2988 B TURNING VANES RECOMM...

Page 18: ...num Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille When used with a ducted supply an ICX28 Cabinet Extension may be used to con...

Page 19: ...he unit in the bottom of the base about 12 in from the front on both the left and right side These holes are covered with insulation and are not visible They are located very close to the side panels...

Page 20: ...pply liberal amount of caulk to back of flange before installing Screws to Attach Unit Fan Shroud Exhaust Sleeve to Use 6 3 4 Long Self Tapping Screws to Attach Inner Sleeve Use 12 3 4 Long to Unit Ba...

Page 21: ...Manual 2100 597G Page 21 of 68 INTERIOR FLOOR I TEC UNIT OUTSIDE WALL FILL INSULATION FILL INSULATION OUTDOOR GRILLE SIZE VARIES INSIDE WALL SLEEVE MIS 2928 A FIGURE 11B Unit Mounting...

Page 22: ...for wire sizing information and maximum fuse or circuit breaker size Each unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of cu...

Page 23: ...0V tap For 208V operation reconnect from 240V to 208V tap The acceptable operating voltage range for the 240 and 208V taps are as noted in Table 3 LOW VOLTAGE CONNECTIONS These units use a grounded 24...

Page 24: ...ry installed jumper Remove jumper and connect to N C fire alarm 3 3 3 2 2 Red W1 E A D L O B Y2 Y1 24V G COM W2 Model CS9BE THO SC SC SC W1 E A D L O B Y2 Y1 24V G COM W2 Model CS9B THO or Completesta...

Page 25: ...tat has Occupancy Signal 5 4 5 CRV Wiring Harness 1 2 2 BROWN WHITE ORANGE BLACK WHITE RED WHITE GND SC SC SC Model CS9BE THO W2 COM G 24V Y1 Y2 O B L D A W1 E GND SC SC SC Model CS9B THO or Completes...

Page 26: ...to A and do not use seperate CO2 controller If CS9B THOC or CS9BE THOC is used connect Brown White 6 Bard 8403 067 GND SC SC SC CO2 Control Model CS9BE THO W2 COM G 24V Y1 Y2 O B L D A W1 E GND SC SC...

Page 27: ...s 1 2 2 BROWN WHITE ORANGE BLACK WHITE RED WHITE PURPLE PINK W1 E A D L O B Y2 Y1 24V G COM W2 Model CS9BE THO SC SC SC W1 E A D L O B Y2 Y1 24V G COM W2 Model CS9B THO or Completestat Model CS9BE THO...

Page 28: ...6 Low Voltage PURPLE PINK 2 3 1 directly to A and do not use seperate CO2 controller If CS9B THOC or CS9BE THOC is used connect Brown White Bard 8403 067 Red GND SC 5 6 Model CS9BE THO W2 COM G 24V Y...

Page 29: ...erm Strip R 6 3 PURPLE PINK 2 1 5 6 Voltage Bard 8403 067 4 3 W1 E A D L O B Y2 Y1 24V G COM W2 CO2 Control Low Model CS9BE THO SC SC SC W1 E A D L O B Y2 Y1 24V G COM W2 Model CS9B THO or Completesta...

Page 30: ...onnect 3 Connect orange wire to G terminal 4 4 ORANGE BLACK WHITE RED WHITE L A W1 E Y2 Y1 Y0 24V G Model CS9BE THOC SC SC SC W2 D Y2 W2 L A W3 7 6 RT G COM O B Completestat Term Strip R D Y1 8 CRV EC...

Page 31: ...ing multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system...

Page 32: ...Since there is a 50 50 chance of connecting power in such a way as to cause rotation in the reverse direction verification of proper rotation must be made Verification of proper rotation direction is...

Page 33: ...on and the alarm relay circuit will energize Recycling the wall thermostat resets the manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120...

Page 34: ...n series with the outdoor fan control thermistor to change the temperature curve that the fan logic control sees It is anticipated that a 2 3 drop in system capacity and efficiency will be seen when t...

Page 35: ...to build up in the structure because there is little or no cooling load Thus the air conditioner is not running enough to remove the excess moisture being brought in Use a control system that in some...

Page 36: ...rical shock Electrical shock can result in serious injury or death Disconnect the remote electric power supply or supplies before servicing corresponding CFM needed for the intake and exhaust blowers...

Page 37: ...CRV Speed Change Terminal Access REMOVE 5 SCREWS FROM CRV DOOR TO ACCESS CRV COMPONENTS MIS 3023 CRV INTAKE BLOWER NOTE CRV EXHAUST BLOWER IS BEHIND INTAKE BLOWER BLOWER SPEED CONTROL LOCATION BLOWER...

Page 38: ...nd are balanced to maintain a slight positive pressurization in accordance to ASHRAE 62 1 Standard The ventilation package is also provided with filters to reduce the required service needed and to fu...

Page 39: ...ith white trace that has as black terminal on the end where it connects to the terminal strip see Figure 23 5 Move the brown wire with white trace to the corresponding CFM level needed in accordance w...

Page 40: ...second stage cooling YO thermostat signal powers relay coil R2 R2 relay then closes NO contact between R and Y1 at low voltage terminal strip engaging stage 1 mechanical cooling NC contacts of relay...

Page 41: ...C CRV only during periods when the conditioned space is occupied Running the ventilation during unoccupied periods wastes energy decreases the expected life of the CRV and can result in large moisture...

Page 42: ...put from CO2 control to Terminal 3 along with pink wire and connect to Terminal 4 along with purple wire of unit low voltage terminal strip 7 Follow the directions supplied with the CO2 control to con...

Page 43: ...ame GREEN STATUS LIGHT blink refer to Step 5 M Terminal ERV MODULATING MODE JUMPER PIN ON P TERMINAL CFM Vdc Signal from CO2 Control 450 10 425 8 87 400 8 31 375 7 61 350 6 73 325 5 91 300 5 15 275 4...

Page 44: ...Manual 2100 597G Page 44 of 68 EXHAUST Return Air Indoor Air VENT Outdoor Air BLOWER BLOWER INTAKE Supply Air VENT SUPPLY BLOWER MIS 3024 FIGURE 25 Ventilation Airflow Diagram...

Page 45: ...age 45 of 68 PLATES MIS 3846 CRV CONTROL PANEL LOCATION CRV DIFFUSER NOTE CRV EXHAUST BLOWER IS BEHIND INTAKE BLOWER REMOVE 5 SCREWS FROM CRV DOOR TO ACCESS CRV COMPONENTS CRV INTAKE BLOWER FIGURE 26...

Page 46: ...allow users to select the transmitter output to be 4 to 20 mA 0 to 5 VDC or 0 to 10 VDC to work with virtually any building management controller An optional relay with user adjustable set points can...

Page 47: ...Select the mounting location away from diffusers lights or any external influences 3 Mount transmitter on a vertical surface to a standard electrical box using the two 6 M2C type screws provided 4 Pu...

Page 48: ...low output range Sets the CO2 concentration for the lowest output 4 mA or 0 VDC Low limit 0 PPM Factory setting 0 PPM High limit 2000 5000 PPM depending on model COH CO2 high output range Sets the CO...

Page 49: ...nt of ventilation required helping to minimize sound levels and ventilation load on the structure CONTROL WIRING The I TEC ERV comes wired from the factory ready to operate in manual mode ON OFF cycli...

Page 50: ...rol panel cover by removing four 4 screws see Figure 30 5 Locate two 0 10Vdc motor control boards in control panel see Figure 31 on page 55 6 On intake motor control board observing GREEN STATUS LIGHT...

Page 51: ...8100 0 5345 5345 0 6480 6480 0 4341 4341 0 90 80 31590 7290 24300 20533 4738 15794 26325 6075 20250 17374 4009 13365 21060 4860 16200 14110 3256 10854 75 21465 7290 14175 13952 4738 9213 17887 6075 1...

Page 52: ...FLOW INDEX or CW to reduce FLOW INDEX to match desired setting Same GREEN STATUS LIGHT blink refer to Step 2 M Terminal ERV MODULATING MODE JUMPER PIN ON P TERMINAL CFM Vdc Signal from CO2 Control 450...

Page 53: ...Manual 2100 597G Page 53 of 68 FIGURE 29 Ventilation Airflow Diagram EXHAUST Return Air Indoor Air VENT Outdoor Air BLOWER BLOWER INTAKE Supply Air VENT SUPPLY BLOWER MIS 3024...

Page 54: ...Page 54 of 68 FIGURE 30 ERV Access ERV DOOR TO ACCESS ERV COMPONENTS ASSEMBLIES REMOVE 5 SCREWS FROM PANEL LOCATION MIS 3025 ERV CONTROL ERV CASSETTE NOTE ERV EXHAUST BLOWER IS BEHIND INTAKE BLOWER E...

Page 55: ...itions In order to achieve a higher level of accuracy the Series CDT includes digital barometric pressure adjustment and the ability to field calibrate the sensor Universal outputs allow users to sele...

Page 56: ...arbon dioxide The mini USB plug of the remote display plugs into the receptor on the side of the housing After a short warm up time the display will begin to show the current temperature and carbon di...

Page 57: ...hPa High limit 32 0 in Hg 1100 hPa ENERGY RECOVERY VENTILATOR MAINTENANCE General Information The ability to clean exposed surfaces within air moving systems is an important design consideration for t...

Page 58: ...of the unit If in a return air filter grille gain access by hinging the grille open 3 Inspect energy recovery ventilator for proper wheel rotation and dirt buildup This can be done in conjunction wit...

Page 59: ...Manual 2100 597G Page 59 of 68 FIGURE 32 Hub Assembly with Ball Bearings...

Page 60: ...29 20 46200 58 16122 96 6383 17 149355 21 44855 59 15710 97 6239 16 144374 22 43554 60 15310 98 6098 15 139576 23 42295 61 14921 99 5961 14 134956 24 41077 62 14544 100 5827 13 130506 25 39898 63 1417...

Page 61: ...nsate Control FIGURE 33 Indoor Condensate Overflow Switch FIGURE 34 Outdoor Condensate Sensor happens on the same cooling call cycle a hard lockout of the compressor circuit will occur See Sequence of...

Page 62: ...otor IS NOT receiving any communication troubleshoot the communication issue using the diagnostic table for the fan logic control a This motor uses a 7 wire harness to control the motor Line power is...

Page 63: ...ssor operation and is normal RED STATUS LIGHT LA Is illuminated when low ambient control switch is in the closed position NOTE This is not required in heat pump operation as the low ambient switch is...

Page 64: ...ine if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow dow...

Page 65: ...tor Verify with a standard ohmmeter that the resistance from each motor lead in the motor plug just removed to the motor shell is 100K ohms Refer to Figure 37 Measure to unpainted motor end plate If a...

Page 66: ...X Pin 15 X X X X X X X X X Pin 16 Not Used POWER CONNECTOR PWB HEADER AMP 1 350945 0 PIN Description 1 Jumper Pin 1 to Pin 2 for 120VAC Line Input Only 2 3 Chassis Ground 4 AC Line 5 AC Line Troublesh...

Page 67: ...gh Side 122 218 123 238 125 258 127 279 128 299 130 319 131 339 133 360 134 380 135 404 136 428 137 452 138 476 139 500 140 524 80 DB 67 WB Low Side High Side 134 217 136 239 138 260 139 282 141 304 1...

Page 68: ...gh Side 126 192 128 212 130 233 132 253 134 274 136 294 138 315 139 335 141 356 142 379 143 402 144 426 145 449 146 472 147 496 80 DB 67 WB Low Side High Side 140 195 141 216 143 236 145 257 146 278 1...

Reviews: