It is important to check the software version
during installation to ensure that the latest
version has been installed. Current software
versions, change log and installation
instructions are available on the Bard website at
http://www.bardhvac.com/software-download/
NOTICE
Program Version
The Program Version screen displays the model number
of the unit as well as all program version information
for the PLC (see Figure 6). This information can be
used to determine whether a software update may be
required based on information found in the software
change log. This change log can be found at http://
www.bardhvac.com/software-download/.
FIGURE 6
Program Version
Menu Screens and Password Levels
A
System Config: A1-A5 User (2000)
B
Adv Sys Config: B1-B4 Technician (1313)
C
I-O Config: Technician (1313)
D
On/Off: User (2000)
E
Alarm Logs: User (1313)
F
Settings
Date/Time: Technician (1313)
Language: User (2000)
Serial Ports: Technician (1313)
Password
Change
Initialization
Alarm Initialization: User (2000)
Default Installation: Engineer (9254)
Parameters Import/Export: Engineer (9254)
Alarm Export: User (2000)
Unit of Measure:
G
Logout: Used to log out of the current password level.
Entering back into the menu requires password.
User
2000
Technician
1313
Engineer
9254
Use UP or DOWN keys and ENTER key to enter password
TABLE 2
LC6000/TEC-EYE Passwords (Defaults)
Alarm Log
The alarm log screens show a log of each alarm. There
will be a log for when alarm occurred and if the alarm
auto clears, it will show when the alarm cleared. See
page 11 for information on clearing alarms.
The passwords listed above are the default passwords.
End users can change these passwords if additional
security is desired.