Manual 2100-665A
Page
47 of 51
Screen
Menu Item
Range
Default Value
Description
On Diff
-999.9 to 999.9
5.0°F
Differential used by outdoor setpoint
OA Humid Set
0-100%
80%
Setpoint to limit economizer operation
Press DOWN Key
A5
Economizer
OA Dew Pt Set
-999.9 to 999.9
55.0°F
Setpoint used to limit economizer
operation
On Diff
-999.9 to 999.9
5.0°F
Differential used by OA dewpoint
setpoint
Dewpoint Delay
0-32767
120 sec
Time delay used for dewpoint conditions
Press DOWN Key
A6
Unit Config
Damper Modulation
Descriptive text
Mixed FC Set
-999.9 to 999.9
55.0°F
Setpoint being used by economizer PID
Gain
-999.9 to 999.9
20.0°F
Proportional gain used by PID
Integral
0-65535
120 sec
Integral time used by PID
Derivative
0-65535
0 sec
Derivative time used by PID
Press DOWN Key
A7
Alarm Config
Heading
Mixed Air Alarms
Descriptive text
Diff Lo
-999.9 to 999.9
10
Low differential for alarm
Diff Hi
-999.9 to 999.9
5.0
High differential for alarm
Del
0-32767
30 sec
Delay for alarm
Low Pressure Alarms
Descriptive text
OAT
-999.9 to 999.9
55.0°F
OAT setpoint for alarm
Diff
-999.9 to 999.9
5.0
Differential for OAT setpoint
Del
0-32767
120 sec
Delay used for alarm (OAT above
setpoint)
LDel
0-32767
180 sec
Delay used for alarm (OAT below
setpoint)
Two Count Del
0-32767
900 sec
Delay before retry counter resets
Press DOWN Key
A8
Alarm Config
Damper Alarms
Open Del
20 sec
Time delay before alarm occurs on fail
to open
Close Del
300 sec
Time delay before alarm occurs on fail
to close
Freeze Alarm
Low Temp
33.0°F
Setpoint for freeze alarm
Reset Temp
55.0°F
Temperature for auto reset of alarm
Reset Del
300 sec
Time delay for auto reset of alarm
Press DOWN Key
A9
Alarm Config
Air Flow Alarm