background image

Manual

2100-435D

Page

29 of 38

the return air thermostat sensed a temperature below 65°
during dehumidification, the fist stage electric heaters
are brought on to raise the return air temperature above
65°.  When the humidistat is satisfied, the system
switches back to normal air conditioning mode.

If the thermostat calls for cooling during
dehumidification mode, the call for cooling takes
precedence over the dehumidification and the unit will
cool until the thermostat is satisfied.  Once the call for
cooling is satisfied, the unit may continue to
dehumidify.

If the thermostat calls for heat when the unit is in the
dehumidification mode, the electric heaters will
energize and the evaporator air flow will return to the
heating air flow.  When the thermostat is satisfied, the
electric heaters will turn off and the air flow will be
reduced and the system will continue to dehumidify
until humidistat is satisfied.

If the unit is running in heat pump mode and the
humidistat calls for dehumidification, the
dehumidification mode takes precedence over the heat
pump heating mode.  The unit will not return to the
heating mode until 2nd stage heating is called for.

The Climate Control 

Option G 

has a non-programmable

electronic thermostat, humidistat and is compatible for
use with a CS2000A Energy Control Monitor.  This unit
has a refrigerant reheat circuit that is controlled by a
three-way valve.

Unit operation is controlled by the thermostat and
humidistat, and optional CS2000A Energy Monitor
Controller can be easily integrated by simple connection
to the low voltage terminal block provided.  See Figure
16C.

NOTE: The CS2000A (or other means for ventilation

control) must be used if any mechanical
(motorized) ventilation options are installed.

Dehumidification can be set to be available only when
CS2000A is active or to be available continuously by
switching a jumper on the relay logic board.  See notes
on Table 12.

When the humidity is above the setpoint of the
humidistat, the compressor circuit and the 3 way valve
are energized and the evaporator air flow is reduced.
The 3 way valve directs hot discharge gas into a
separate desuperheating condenser circuit that reheats
the conditioned air before it is delivered to the room.  If
the return air thermostat sensed a temperature below 65°
during dehumidification, the fist stage electric heaters
are brought on to raise the return air temperature above
65°.  When the humidistat is satisfied, the system
switches back to normal air conditioning mode.

If the thermostat calls for cooling during
dehumidification mode, the call for cooling takes
precedence over the dehumidification and the unit will
cool until the thermostat is satisfied.  Once the call for
cooling is satisfied, the unit may continue to
dehumidify.

If the thermostat calls for heat when the unit is in the
dehumidification mode, the electric heaters will
energize and the evaporator air flow will return to the
heating air flow.  When the thermostat is satisfied, the
electric heaters will turn off and the air flow will be
reduced and the system will continue to dehumidify
until humidistat is satisfied.

If the unit is running in heat pump mode and the
humidistat calls for dehumidification, the
dehumidification mode takes precedence over the heat
pump heating mode.  The unit will not return to the
heating mode until 2nd stage heating is called for.

REFRIGERANT TUBE SCHEMATIC FOR
REHEAT COIL

Figure 20 shows the refrigerant gas flow through the
reheat coil during the dehumidification mode.

When the unit is in standard cooling (Figure 21) or
heating mode the reheat coil is inactive.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure curves can be found later in the
manual covering all models on both cooling and heating
cycles.  It is imperative to match the correct pressure
curve to the unit by model number.  Upper and lower
service doors must be attached to obtain proper reading.

FIGURE 19

LOW PRESSURE CONTROL BYPASS TIMER

MIS-1917

Summary of Contents for QTEC QH303D

Page 1: ...QH423D QH483D QH603D QTEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 435D Supersedes 2100 435C...

Page 2: ...ation 23 Service Hints 24 Mist Eliminator Service 24 Vent Options 25 Sequence of Operation 28 Optional Climate Controls Sequence of Operation 28 Refrigerant Tube Schematic for Reheat Coil 29 Pressure...

Page 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Page 4: ...otorized w Exhaust Spring Return FILTER OPTIONS X 1 Inch Fiberglass Standard F 2 Inch Fiberglass P 2 Inch Pleated COLOR OPTIONS V Platinum w Slate Front Vinyl 4 Gray paint TABLE 1 FACTORY BUILT IN ELE...

Page 5: ...R E W O P E R I W E Z I S 2 D N U O R G E R I W E Z I S 3 M U M I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z...

Page 6: ...Z 0 B D 3 8 4 H Q 6 0 B D 9 0 B D 5 5 1 B D 3 8 0 2 0 3 2 1 1 1 1 6 2 4 4 3 5 3 5 0 4 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C D 3 8 4 H Q 6 0 C D 9 0 C D 5 5 1 C D 3 0 6 4 1 1 1 1 4 1 3 2 7 2 7 2 5...

Page 7: ...Manual 2100 435D Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...

Page 8: ...e removed and discarded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skit until the front wheels hang over the edge...

Page 9: ...ructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and an...

Page 10: ...NG 8 FT 6 IN MINIMUM RECOMMENDED CEILING HEIGHT 8 FT 5 IN FLOOR MIS 1573 SUSPENDED CEILING FIXED CEILING DUCT DUCT FLANGE 8 FT 7 IN MINIMUM RECOMMENDED CEILING HEIGHT 7 FT 4 IN UNIT HEIGHT 12 IN MINIM...

Page 11: ...free blow with the use of QPB Plenum Box or a duct supply air system For hot water coil options a QPBHW F for free blow or QPBHW D for ducted airflow is used The QPB and QPBHW Plenum Box mounts on top...

Page 12: ...nnections on the unit The rear drain is the primary drain and is located on the right lower rear panel of the unit The optional side drain is located on the bottom right side of the unit The side drai...

Page 13: ...ice This indicates that the unit needs to be serviced MIS 1061 FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS MIS 1576 CABINET SIDE PA...

Page 14: ...keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel o...

Page 15: ...that amount of current Depending on the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable...

Page 16: ...under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Removing the Y compressor signal alone turns the compressor off but does not activa...

Page 17: ...S s e r u t a e F t n a n i m o d e r P 8 1 0 3 0 4 8 4 2 0 1 N 4 7 8 T 0 1 0 4 0 4 8 1 6 2 1 4 7 6 Q 2 l o o C t a e H c i t a m o t u A n o i t i s o P r e v o e g n a h C 8 3 0 3 0 4 8 A 0 0 6 H A...

Page 18: ...3 4 5 6 7 8 9 10 11 12 Y1 G E 7 6 5 4 3 2 1 Plug 4 8 B W2 R C L 12 11 10 9 Brown Blue W1 W1 Y1 W1 L C R W2 L C R W2 B B E1 G A1 Y1 4 3 5 6 Y G O1 4 E 5 6 Blue Red Red Yellow Tan Orange Yellow Blue Br...

Page 19: ...ns to control ventilation must be used if any of the mechanical motorized ventilation options are installed DEHUM CIRCUIT 24 VAC COM DEHUM CIRCUIT COMPRESSOR NOTE FIELD SUPPLIED DEHUMIDISTAT MUST BE D...

Page 20: ...n Blue Yellow Orange Tan Orange Red Red Red Red Black Black Black Red 2 3 1 2 3 4 5 6 7 8 9 10 11 12 7 6 5 4 3 2 1 Plug 4 8 12 11 10 9 Brown Blue W1 L C R W2 B E1 G A1 Y1 Blue Red Red Tan Orange Yello...

Page 21: ...n Blue Yellow Orange Tan Orange Red Red Red Red Black Black Black Red 2 3 1 2 3 4 5 6 7 8 9 10 11 12 Y1 G 7 6 5 4 3 2 1 Plug 4 8 B W2 R C L 12 11 10 9 Brown Blue W1 4 3 5 6 Blue Red Red Yellow Tan Ora...

Page 22: ...4 3 2 1 Plug 4 8 B W2 R C L 12 11 10 9 Brown Blue W1 4 3 5 6 Blue Red Red Yellow Tan Orange Yellow Blue Brown Red Black H200 Humidistat T8511 Thermostat Yellow E C Y1 Y O1 Terminal Block 1 Black Red...

Page 23: ...nitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED w...

Page 24: ...cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to...

Page 25: ...h the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed QTEC R ENERGY RECOVERY VENTILATOR Option Before starti...

Page 26: ...Manual 2100 435D Page 26 of 38 MIS 1627 FIGURE 17 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Page 27: ...Manual 2100 435D Page 27 of 38 MIS 1039 FIGURE 18 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Page 28: ...ion can be restored by turning of the main power supply off and then back on or reset the room thermostat The low pressure control has a bypass to eliminate nuisance lockout on cold start up The bypas...

Page 29: ...humidity is above the setpoint of the humidistat the compressor circuit and the 3 way valve are energized and the evaporator air flow is reduced The 3 way valve directs hot discharge gas into a separa...

Page 30: ...Manual 2100 435D Page 30 of 38 FIGURE 20 QTEC DEHUMIDIFICATION MODE CIRCUIT DIAGRAM MIS 1088...

Page 31: ...Manual 2100 435D Page 31 of 38 FIGURE 21 QTEC COOLING MODE CIRCUIT DIAGRAM MIS 1089...

Page 32: ...a 0 coil temperature This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region Use a small screwdriver or other metallic object o...

Page 33: ...p a c d e t r o h s r o n e p o r o t i c a p a c e c a l p e R l o r t n o c p m u p t a e H e v i t c e f e d t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p C N m o C l o r...

Page 34: ...3 9 8 0 0 1 9 9 3 1 8 8 1 7 3 5 8 9 9 6 2 8 1 2 1 0 8 2 3 6 7 7 0 3 2 5 7 0 1 9 2 7 0 7 6 0 7 7 0 5 8 6 8 1 4 6 6 9 9 3 4 6 9 4 4 2 6 5 6 5 0 6 5 4 7 8 5 0 3 1 0 4 1 0 5 1 0 6 1 0 7 1 0 8 1 0 9 1 0 0...

Page 35: ...ing performance will occur with a refrigerant charge resulting in a Super Heat as shown in Table 8 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating...

Page 36: ...L e d i S h g i H 4 7 2 1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9 3 2 1 8...

Page 37: ...2 2 3 6 3 H Q g e d 0 7 e d i S w o L e d i S h g i H 3 1 7 4 1 7 1 3 5 1 1 2 9 5 1 5 2 4 6 1 7 2 7 6 1 0 3 1 7 1 4 3 6 7 1 8 3 2 8 1 2 4 8 8 1 6 4 4 9 1 2 5 2 0 2 5 5 6 0 2 9 5 1 1 2 3 6 7 1 2 3 2 4...

Page 38: ...a jumper on it to choose between fulltime dehumidification and occupied dehumidification only With the jumper in the 1 2 position dehumidification is available fulltime With the jumper in the 2 3 posi...

Reviews: